Furthermore, different fieldbus interface states can be requested via the ACExC 01.2

display (Menu 

Diagnostic M0022

). For further information, please refer to “Manual

(Device integration fieldbus) AC 01.2/ACExC 01.2”.

4.2.1

Line and star topology

Table 5:

Troubleshooting table

Causes and remedies

 Continue with 4

Yes

Can actuator be controlled

via fieldbus?

1

 Continue with 2

No

FO coupler supplied with voltage (24 V DC).

 Continue with 4

Yes

Green LED [U

L

] illumina-

ted?

2

 Continue with 3

No

Possible causes and remedies:

FO coupler is defective

 Replace coupler.

Power supply (24 V DC)

available?

Verify power supply

(24 V DC) of the FO

coupler:

3.

Remedies:

 Check fuses within ACExC 01.2.

 Restore power supply.

Power supply (24 V DC)

not available?

Possible causes:

Sender on coupler defective

FO connection of sender not operable

Yes

Is yellow LED [BA] flicke-

ring?

4

Possible causes:

Slave not properly connected

Slave defective

Master defective

FO coupler receiver or FO connection of receiver defective

Is the required FO coupler (BARTEC order no.: 07-7311-

97WP/6000 or /4000) installed at the master?

No

4.2.2

Ring topology

Troubleshooting

Is the connection between FO coupler and device correct?

Have all screw-type terminals been tightened correctly?

Has the proper interface been selected?

Is the transmission distance too long?

Is the optical sender connected to the optical receiver of the opposite device?

Are the bus termination resistors activated?

Is an FO coupler, type BARTEC 07-7311-97WP/5400, connected to the fieldbus

master?

Is there more than one master module in the ring?

Table 6:

Troubleshooting table

Causes and remedies

No fault

Yes

Can actuator be controlled

via fieldbus?

1

 Continue with 2

No

FO coupler supplied with voltage (24 V DC).

 Continue with 6

Yes

Green LED [U

L

] illumina-

ted?

2

 Continue with 3

No

Possible causes and remedies:

FO coupler is defective

 Replace coupler.

Power supply (24 V DC)

available?

Verify power supply

(24 V DC) of the FO

coupler:

3.

Remedies:

 Check fuses within ACExC 01.2.

 Restore power supply.

Power supply (24 V DC)

not available?

13

Corrective action

Содержание AUMATIC ACExC

Страница 1: ...hort instructions do NOT replace the operation instructions They are only intended for persons already familiar with the operation instructions where safety instructions assembly operation and commiss...

Страница 2: ...ologies 8 3 1 Line topology 9 3 2 Star topology 10 3 3 Ring topology two fibre ring 12 4 Corrective action 12 4 1 LED indications 12 4 2 Troubleshooting 13 4 2 1 Line and star topology 13 4 2 2 Ring t...

Страница 3: ...ifferent topologies are possible Line topology Star topology Redundant ring topology Apart from the large distances FO cables offer further advantages In environments with electromagnetic interference...

Страница 4: ...he defined position Protect unused FO cable connections against contamination or dust with protec tive caps plugs supplied by the factory Connect incoming FO cable with the optical receiver the outgoi...

Страница 5: ...afety or in type of protection Ex d flameproof enclosure Hereby the flameproof interior compartment of the actuator Ex d remains closed 2 Insert cable glands with Ex e approval and suitable for connec...

Страница 6: ...e FO coupler on fixing plate in parking position Figure 4 FO coupler in parking position 3 Insert FO cables through cable glands 4 Link FO connectors crosswise Optical output of actuator 1 with optica...

Страница 7: ...flameproof Preserve joint surfaces with an acid free corrosion protection agent 3 Check whether O ring 3 is in good condition replace if damaged 4 Apply a thin film of non acidic grease e g petroleum...

Страница 8: ...Baud rate kbit s 36 9 6 36 19 2 36 45 45 36 93 75 18 187 5 9 500 4 1 500 Special features of line topology The optical signal is converted into an electrical signal at each device Prior to transmissi...

Страница 9: ...echnical data 1 FO PP coupler within electrical connection of ACExC 01 2 2 LWL Stich Koppler in der Leittechnik zwingend erforderlich 3 LWL Stich Koppler f r Beliebiges Profibus DP Feldger t 4 Any Pro...

Страница 10: ...n optical line and all actuators remain available If one module fails i e when power supply is interrupted only the actuator connected to this module is disconnected from the ring the remaining networ...

Страница 11: ...0 90 900 500 2 6 2 40 900 187 5 2 6 4 80 900 93 75 2 6 9 90 900 45 45 2 6 23 44 900 19 2 2 6 46 88 900 9 6 The FO coupler connected to the master via copper cable has to be a master module Only one ma...

Страница 12: ...orange Both channels do not receive any signal oran ge LED is not illuminated Input cables to the two adjacent FO couplers are in perfect condition Information If the fault LED F is illuminated red y...

Страница 13: ...ler receiver or FO connection of receiver defective Is the required FO coupler BARTEC order no 07 7311 97WP 6000 or 4000 installed at the master No 4 2 2 Ring topology Troubleshooting Is the connectio...

Страница 14: ...O coupler fieldbus device Connector ok 5 Remedies Correct connection connect optical output to optical input No Possible causes and remedies Sender at coupler defective FO connection of sender not ope...

Страница 15: ...cable damping max 3 0 dB km without additional damping 850 nm Wave length 25 C to 60 C Operation temperature 24 V DC 75 mA internally supplied via power supply unit of ACExC 01 2 For line and star to...

Страница 16: ...ing FO couplings at electrical connection of AUMA actuators damping of these actuators is already included in the optical budget aL Specific cable damping dB km refer to technical data of the FO cable...

Страница 17: ...49 7931 597 0 Fax 49 7931 597 119 www bartec de FO cables and wires Network reliability despite multiple points of failure eks Engel GmbH Co KG Sch tzenstr 2 57482 Wenden Hillmicke Tel 49 2762 9313 6...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...r GmbH Co KG P O Box 1362 D 79373 Muellheim Tel 49 7631 809 0 Fax 49 7631 809 1250 riester auma com www auma com Y005 741 003 en 1 13 For detailed information on AUMA products refer to the Internet ww...

Отзывы: