12.
Technical data
Information
The following technical data includes standard and optional features. For detailed
information on the customer-specific version, refer to the order-relevant data sheet.
This data sheet can be downloaded from the Internet at http://www.auma.com in
German and English (indication of commission number required).
12.1
Features and functions of actuator
Standard:
●
II2G Ex de IIC T4
●
II2D Ex tD A21 IP6x T130°C
●
II2G c IIC T4
For actual version, refer to actuator name plate.
Explosion protection
PTB 01 ATEX 1119
EC type examination certificate
●
Ex d flameproof enclosure:
-
Motor compartment
-
Switch compartment
-
Controls housing
-
Terminal compartment (for electrical connection: KES-Exd)
●
Ex e increased safety:
-
Terminal compartment (for electrical connections: KP, KPH, KES)
●
c constructional safety:
-
Gear housing
Protection types
SG: Short-time duty S2 - 10 min
Type of duty
1)
Refer to actuator name plate
Torque range
Refer to actuator name plate
Operating time for 90°
Standard: 3-ph AC asynchronous motor, type IM B9 according to IEC 60034
Motor
Standard: F, tropicalized
Option: H, tropicalized
Insulation class
Standard: PTC thermistors (according to DIN 44082)
Option: Thermoswitches (NC)
Motor protection
Yes
Self-locking
Standard:
80° to 110° adjustable between min. and max. values
Option:
30° – 40°, 40° – 55°, 55° – 80°, 110° – 160°, 160° – 230° or 230° – 320°
Swing angle
Counter gear mechanism for end positions CLOSED and OPEN
Standard:
●
Single switches (1 NC and 1 NO; not galvanically isolated) for each end position
Options:
●
Tandem switches (2 NC and 2 NO) for each end position, switches galvanically isolated
●
Triple switches (3 NC and 3 NO) for each end position, switches galvanically isolated
●
Intermediate position switches (DUO limit switching), adjustable for any position
Limit switching
Torque switching adjustable for directions OPEN and CLOSE
Standard:
Single switch (1 NC and 1 NO; not galvanically isolated) for each direction
Option:
Tandem switches (2 NC and 2 NO) for each direction, switches galvanically isolated
Torque switching
Potentiometer or 0/4 – 20 mA (RWG)
Position feedback signal, ana-
logue (option)
Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED
Mechanical position indicator
Blinker transmitter
Running indication
Standard: Resistance type heater, 5 W, 24 V DC, (internal supply)
Heater in switch compartment
Voltages: 110 – 220 V AC, 220 – 240 V AC or 400 V AC
Power: 12.5 W
Motor heater (option)
68
SGExC 05.1 – SGExC 12.1 Control unit: electromechanic
Technical data
ACExC 01.2 Intrusive Modbus RTU
Содержание AUMATIC ACExC 01.2
Страница 84: ...84 SGExC 05 1 SGExC 12 1 Control unit electromechanic Certificates ACExC 01 2 Intrusive Modbus RTU...
Страница 85: ...85 SGExC 05 1 SGExC 12 1 Control unit electromechanic ACExC 01 2 Intrusive Modbus RTU Certificates...
Страница 86: ...86 SGExC 05 1 SGExC 12 1 Control unit electromechanic ACExC 01 2 Intrusive Modbus RTU...
Страница 87: ...87 SGExC 05 1 SGExC 12 1 Control unit electromechanic ACExC 01 2 Intrusive Modbus RTU...