![AUMA ACE C 01.2 Profinet Series Скачать руководство пользователя страница 72](http://html1.mh-extra.com/html/auma/ace-c-01-2-profinet-series/ace-c-01-2-profinet-series_manual_3016379072.webp)
Open
1.
Loosen screws [2] and remove cover [1] from the switch compartment.
Close
2.
Clean sealing faces of housing and cover.
3.
Preserve joint surfaces with an acid-free corrosion protection agent.
4.
Check whether O-ring [3] is in good condition, replace if damaged.
5.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
6.
Place cover [1] on switch compartment.
7.
Fasten screws [2] evenly crosswise.
11.2.
Mechanical position indicator (self-adjusting)
Figure 80: Mechanical position indicator (self-adjusting)
The self-adjusting mechanical position indicator shows the valve position by means
of an arrow
. When correctly set, the arrow points to symbol
(OPEN) or
(CLOSED) in the end positions.
Information
The position indications is housed in the actuator switch compartment. Opening the
switch compartment for manual setting is only necessary if the gear stage setting
must be modified of if the factory settings of predefined end position CLOSED (or
OPEN) must be adapted when commissioning.
11.2.1.
Mechanical position indicator: set
1.
Move valve to end position CLOSED.
2.
Push both lower discs with the symbols
(OPEN) and
(CLOSED) towards
each other. The disc with the arrow is thereby
is driven:
Figure 81: Setting position in CLOSED
72
SAEx 07.2 – SAEx 16.2/SAREx 07.2 – SAREx 16.2 Control unit: electronic (MWG)
Commissioning (settings/options in the actuator)
ACExC 01.2 Non-Intrusive HART