AUKS Light CAC R22 60Hz T3 Controller
33
Table 1 Air treatment temperature process of a fan coil
2. Methods of product selection
Enthalpy difference correction
Make corrections based m-the ratio between the enthalpy difference during actual operation
and that at standard condition, and calculate the actual cooling capacity of the fan coil, then
select the correct fan coil based on actual cooling capacity.
Q`=QH· (
△
Im/
△
IH)=mQH
where: Q` —— Actual cooling capacity of a fan coil
(
W
)
.
QH—— Rated cooling capacity at of a fan coil at standard condition
(
W
)
.
△
Im —— Actual air treatment enthalpy difference of a fan coil
(
W/kg
)
△
IH——Air treatment enthalpy difference of a fan coil at standard condition
(
W/kg
)
m —— Correction coefficient
Airflow based type selection
Select a fan coil based on the air conditioning flow calculated by the cooling load of air
conditioning and the actual air treatment enthalpy difference of the fan coil.
G=Q/
△
Im· (W)
where: G——Air conditioning flow kg/h
Besides, when the water supply temperature, temperature difference of supply and return
water, water supply and inlet air temperature are different than those of the standard
condition, further correction is required based on the information.
Содержание AFC-1000CF/4
Страница 1: ...1 Technical Manual Fan Coil Unit Ceiling Floor Type...
Страница 3: ...AUKS Fan CoilGeneral description 3 Part 1 General description 1 Nomenclature...
Страница 14: ...AUKS Fan CoilUnit information 14 4 Demension AFC 400CF 4 AFC 500CF 4 AFC 600CF 4 AFC 800CF 4 AFC 1000CF 4...
Страница 15: ...AUKS Fan CoilUnit information 15 5 Electrical wiring and connection...
Страница 22: ...AUKS Fan CoilUnit information 22 7 Explode view AFC 400CF 4 AFC 500CF 4...
Страница 30: ...AUKS Fan CoilUnit information 30...
Страница 53: ...Service Manual 53 6 Failure analysis Wired controller communication failure...
Страница 54: ...Service Manual 54 Drainage system failure...
Страница 55: ...Service Manual 55 No action after power on...
Страница 56: ...Service Manual 56 Poor Performance during Unit Operation...
Страница 57: ...Service Manual 57...
Страница 58: ...Service Manual 58 Abnormal sound or vibration...
Страница 59: ...Service Manual 59 Abnormal odor...
Страница 60: ...Service Manual 60 Air conditioner water leakage...