background image

AUKS Fan CoilUnit information

11

variable working condition performance parameter table (continued)

Unit: W

Air inlet temperature

27

DB/19. 5

WB

28

DB/22

WB

Water inlet temperature

5

7

9

5

7

9

Model

(CFM)

Water

flow

(kg/h)

Water

pressure

drop

(kPa)

TH

SH

TH

SH

TH

SH

TH

SH

TH

SH

TH

SH

400

430

8.1

2714

2012

2403

1863

2213

1856

3402

2522

3078

2386

2781

2062

550

11.5

3119

2255

2768

2079

2410

1971

3902

2821

3551

2668

3200

2313

650

15.5

3699

2430

3267

2228

2849

2112

4577

3006

4199

2863

3780

2483

750

20

4037

2511

3618

2282

3161

2140

5063

3149

4617

2911

4131

2570

500

600

18

3385

2510

2998

2324

2761

2316

4244

3146

3840

2977

3470

2572

700

24

3891

2813

3453

2594

3007

2458

4868

3519

4430

3328

3992

2886

800

30

4615

3032

4076

2779

3555

2635

5710

3751

5238

3571

4716

3098

900

37

5036

3133

4514

2847

3944

2671

6316

3929

5760

3632

5154

3206

600

750

21.5

4055

3006

3591

2784

3307

2774

5084

3769

4600

3566

4156

3081

850

26.8

4659

3369

4135

3106

3600

2944

5829

4214

5305

3985

4780

3456

950

32.7

5528

3631

4882

3329

4258

3156

6839

4493

6274

4278

5649

3711

1050

39

6031

3752

5406

3409

4723

3198

7564

4706

6899

4350

6173

3840

800

900

14.8

5988

4439

5303

4111

4883

4096

7508

5565

6793

5266

6137

4549

1100

21

6883

4976

6108

4588

5318

4349

8611

6225

7836

5887

7061

5105

1300

28

8163

5363

7210

4916

6288

4661

10100

6635

9266

6318

8342

5480

1500

36

8909

5542

7985

5035

6976

4724

11173

6950

10190

6426

9117

5672

1000

1200

23

7490

5552

6633

5142

6108

5124

9391

6961

8496

6587

7676

5690

1400

30

8608

6223

7639

5739

6652

5439

10769

7785

9800

7362

8831

6385

1600

38

10210

6708

9018

6149

7865

5830

12633

8299

11589

7902

10434

6854

1800

46.8

11142

6931

9987

6298

8726

5908

13974

8693

12745

8037

11403

7094

Содержание AFC-1000CF/4

Страница 1: ...1 Technical Manual Fan Coil Unit Ceiling Floor Type...

Страница 2: ...Service Manual 2 Contents Part 1 General description 3 Part 2 Unit 5 Part 3 Product selection 31 Part 4 Controller 34 Part 5 Trouble shooting 43...

Страница 3: ...AUKS Fan CoilGeneral description 3 Part 1 General description 1 Nomenclature...

Страница 4: ...AUKS Fan CoilGeneral description 4 2 Unit appearance Series Range of the Air Volume CFM Ceiling Floor 400CFM 500CFM 600CFM 800CFM 1000CFM...

Страница 5: ...AUKS Fan CoilUnit information 5 Part 2 Unit 1 Feature 6 2 Specfication 8 3 Capacity amendment 10 4 Demension 14 5 Electrical wiring and connection 15 6 Installation 17 7 Explode view 22...

Страница 6: ...r on the floor With Setting or Auto two operation modes multi fan speed makes you feel more comfortable Shell was formed by mold and the appearance is slim elegant fashion and comfortable Special insu...

Страница 7: ...old wind Afterheat wind blowing Timing ON OFF Operation Time display Operation mode display Fan speed display Timing ON OFF display Wind angle display Sleeping mode display Health Washable air filter...

Страница 8: ...620 800 980 Hydraulic Resistance kPa 16 20 22 Max Working pressure MPa 1 6 1 6 1 6 Dimension W D H Net mm 929 660 205 929 660 205 1280 660 205 Packing mm 1010 720 280 1010 720 280 1360 720 280 Net Gr...

Страница 9: ...1580 Hydraulic Resistance kPa 30 40 Max Working pressure MPa 1 6 1 6 Dimension W D H Net mm 1280 660 205 1631 660 205 Packing mm 1360 720 280 1710 720 280 Net Gross Weight kg 33 38 44 50 Inlet Outlet...

Страница 10: ...61 2863 2341 800 30 4312 2931 3807 2695 3284 2341 4413 3065 3908 2830 3385 2510 900 37 4750 3015 4228 2762 3638 2392 4868 3167 4278 2914 3756 2543 600 750 21 5 3833 2905 3389 2724 2905 2381 3914 3066...

Страница 11: ...1 5238 3571 4716 3098 900 37 5036 3133 4514 2847 3944 2671 6316 3929 5760 3632 5154 3206 600 750 21 5 4055 3006 3591 2784 3307 2774 5084 3769 4600 3566 4156 3081 850 26 8 4659 3369 4135 3106 3600 2944...

Страница 12: ...4138 4973 6642 8276 9946 900 37 3819 4707 5559 7282 9023 10763 3481 4334 5222 6945 8685 10426 600 750 21 5 3770 4622 5495 7199 8903 10628 3429 4302 5133 6858 8584 10288 850 26 8 4047 4963 5900 7731 95...

Страница 13: ...37 3321 4174 5044 6767 8508 10248 3126 3996 4849 6589 8330 10088 600 750 21 5 3280 4111 4963 6688 8413 10096 3088 3919 4792 6518 8222 9926 850 26 8 3493 4430 5346 7199 9031 10884 3301 4238 5154 6986 8...

Страница 14: ...AUKS Fan CoilUnit information 14 4 Demension AFC 400CF 4 AFC 500CF 4 AFC 600CF 4 AFC 800CF 4 AFC 1000CF 4...

Страница 15: ...AUKS Fan CoilUnit information 15 5 Electrical wiring and connection...

Страница 16: ...imary of transformer Electric heater Line for electric heater Line insert Heat water valve Cold water valve Water pump Indoor fan output High Mid Low Neutral 4 DIP switch Water level switch Air return...

Страница 17: ...g which there shall be no attrition between the mechanical parts and no leakage in the electrical parts d Each fan coil shall undergo water pressure testing with the testing intensity equaling 1 5 tim...

Страница 18: ...d table for incoming equipments Installation precaution Considerations of noise and vibration a Canvass joints shall be installed between the machine and the air return feed pipes to prevent secondary...

Страница 19: ...spension foundation is a structure of either wooden frame or reinforced concrete It must be firm and reliable to bear at least 4 times weight of itself and capable of bearing vibration for long period...

Страница 20: ...y of telephone or lighting rod nor to the earth line of other devices Others Please connect the power cord according to the instructions of the circuit diagram Securely and firmly connect the wires to...

Страница 21: ...y normally 4 Activate the cooling mode check if the unit blows out cool air and discharge water normally 5 Press other buttons of the remote control to check if the unit operates normally 6 After the...

Страница 22: ...AUKS Fan CoilUnit information 22 7 Explode view AFC 400CF 4 AFC 500CF 4...

Страница 23: ...g assembly 1 17 16324012000126 FP 68ZD 3R Evaporator assembly 1 18 16420005000005 ALCe H18A4 C5 Sway a breeze leaf 1 19 16420014000016 ALCe H18A4 C5 The crest covers plank 1 20 16428001000023 ALCe H18...

Страница 24: ...ding assembly 1 17 16324012000097 FP 85ZD Evaporator assembly 1 18 16420005000005 ALCe H18A4 C5 Sway a breeze leaf 1 19 16420014000016 ALCe H18A4 C5 The crest covers plank 1 20 16428001000023 ALCe H18...

Страница 25: ...2 2 16420010000002 ALCe H24B4 C5 Air inlet grill white 2 3 16420012000003 ALCe H24B4 C5 In the center filter net 1 4 16420010000003 ALCe H24B4 C5 Air inlet grill white 1 5 16420015000002 ALCe H24B4 C5...

Страница 26: ...r 1 26 16430001000022 ROHS 35BYJ46 QC50 Step motor 1 27 16420008000003 ALCe H24B4 C5 A Connect a pole 1 16420008000004 ALCe H24B4 C5 B Connect a pole 1 28 16420007000008 ALCe H24B4 C5 Perpendicular bl...

Страница 27: ...H24B4 C5 Sway a breeze leaf 1 22 16420014000009 ALCe H24B4 C5 The crest covers plank 1 23 16428001000019 ALCe H24B4 C5 Topmost foam 1 24 16420006000004 ALCe H24B4 C5 Air guide louver assembly 1 25 16...

Страница 28: ...02 ALCe H24B4 C5 Left side adornment plank 1 6 16421038000009 ALCe H24B4 C5 The electricity controls a box 1 7 16421005000205 ALCe H24B4 C5 The electricity controls a box of cover 1 8 11220544000008 R...

Страница 29: ...A Connect a pole 1 16420008000005 ALCe H42A5 C5 Connect a pole 1 28 16420007000008 ALCe H24B4 C5 Perpendicular blade 21 29 16428001000018 ALCe H24B4 C5 Right foam 1 30 16321006000006 ALCe H24B4 C5 Bra...

Страница 30: ...AUKS Fan CoilUnit information 30...

Страница 31: ...AUKS Light CAC R22 60Hz T3 Controller 31 Part 3 Product selection 1 Precautions of product selection 32 2 Methods of product selection 33...

Страница 32: ...increases as cooling capacity decreases without much change in power consumption of unit cooling capacity e When the temperature difference between inlet and outlet water of a fan coil increases the w...

Страница 33: ...ity at of a fan coil at standard condition W Im Actual air treatment enthalpy difference of a fan coil W kg IH Air treatment enthalpy difference of a fan coil at standard condition W kg m Correction c...

Страница 34: ...Light CAC R22 60Hz T3 Controller 34 Part 4 Controller 1 General information Remote controller wired controller display panel Remote controller Wired controller Display panel 2 Standard Optional Stand...

Страница 35: ...Dehumidify Heating TEMP button and TEMP button Temperature adjustment range 16 32 FAN button Change the fan speed will change in turn as Low Medium High Auto SWING button 1 Press this button for the f...

Страница 36: ...d air velocity display screen displays all presetting parameters and remains constant after reaching presetting time air conditioner will automatically start as per presetting state After setting timi...

Страница 37: ...e activated 1 After the setting of sleeping mode the cooling operation enables the set temperature to increase 1 after 1 hour and another 1 auto matically after 1hour 2 After the setting of sleeping m...

Страница 38: ...ner by depressing the ON OFF button 2 Depress the MODE button to select COOLING mode 3 Depress the SET button to adjust the temperature setting with the range of 16 32 and increment of 1 4 Depress air...

Страница 39: ...the desired time Depress the timing button again to set the function of Timer ON Depress other function buttons to set the operation condition after the starting of the air conditioner including mode...

Страница 40: ...push the button one time then the operation modes will change in turn as below Auto Cooling Dehumidify Heating Temp button and Temp button Press the button can adjust temperature Temperature adjustme...

Страница 41: ...tch mode Health mode SLEEP button 1 Press the button to the sleeping indicator light of indoor unit flashes on 2 After the setting of sleeping mode the cooling operation enables the set temperature to...

Страница 42: ...e presetting time it will implement corresponding timing operation 2 After setting time of timing ON and OFF pressing Timer button can cancel timing 3 Enter into time setting state of timing function...

Страница 43: ...on 43 Part 5 Trouble shooting 1 Electrical system main components 44 2 Main functions of the unit 44 3 Poor efficiency explanation 39 4 Electric components malfunction inspection 39 5 DIP setting and...

Страница 44: ...mode 5 The mode once selected will not change as the indoor temperature varies however by turning off and then on the unit or switching the mode the operation mode can be reselected 2 2 Cooling opera...

Страница 45: ...to low speed to avoid speed fluctuation 1 1 Tset 2 Setting fan speed Auto fan speed High speed Low speed Fan stops Cooling electric valve closes Cooling electric valve opens Middle speed Fan stops Lo...

Страница 46: ...ration of the indoor fan will be activated 40 seconds after 5 minutes if TA TS 2 the indoor fan will remain stopped for 5minutes before reactivate low speed operation for 40 seconds otherwise the rela...

Страница 47: ...ivated 40 seconds after 5 minutes if TA TS 2 is satisfied the indoor fan will remain stopped for 5minutes before reactivate low speed operation for 40 seconds otherwise the related heating operation w...

Страница 48: ...n of the cooling air oscillating is 30 degree backward from wide open position the final position is wide open position The initial position of the heating air oscillating is wide open position the fi...

Страница 49: ...ition is 50 degree backward from wide open position The initial position of the Heating air oscillating is 50 degree backward from wide open position the final position is 90 degree backward from wide...

Страница 50: ...air speed and the sleeping indicator will light After the sleeping mode is activated by depressing sleeping button the temperature setting will automatically increase by 1 after 1h under cooling mode...

Страница 51: ...d out etc It is not malfunction need to find out the causing if the causing is the electricity net voltage is too low user should load a power manostat to keep voltage between 220V 380V for AC normall...

Страница 52: ...shielded Protection normal ON 4 DIP 3 Power fail memory Yes No OFF 4 DIP 4 Heating selection Single electric heating Water valve electric heating OFF When water valve electric heating are operating t...

Страница 53: ...Service Manual 53 6 Failure analysis Wired controller communication failure...

Страница 54: ...Service Manual 54 Drainage system failure...

Страница 55: ...Service Manual 55 No action after power on...

Страница 56: ...Service Manual 56 Poor Performance during Unit Operation...

Страница 57: ...Service Manual 57...

Страница 58: ...Service Manual 58 Abnormal sound or vibration...

Страница 59: ...Service Manual 59 Abnormal odor...

Страница 60: ...Service Manual 60 Air conditioner water leakage...

Отзывы: