INSTALLATION
PRIMO PILOT
MANUAL
-
15
5 - SET-UP
Ensure that:
- All works carried out on the hydraulic circuits and the electrical
circuits are in compliance with the regulations in effect
(inspection by a qualifi ed professional)
- The pressure relief valve on the cold water inlet of the domestic
hot water tank (if the installation has a domestic hot water
tank) is working properly and is properly connected to a drain
in compliance with the regulations in eff ect.
- All piping is watertight.
- All hydraulic connections are properly tightened.
- The correct voltage at the mains switch.
- All of the valves are open and nothing is obstructing the
circulation of water in the exchanger and in the hydraulic
circuit.
- The installation is equipped with a fi lter valve or a fi lter on its
inlet and that the fi lter is not clogged.
- The automatic air purger’s cap is open.
- The exterior sensor and the ambient temperature control (if
present on the installation) are connected properly.
- If using an ambient thermostat, ensure that it is actually being
used.
Once all of these checks have been done, turn on the heat pump
and
PRIMO Pilot
.
5.1 - Before set-up
Set-up must be done by a qualifi ed
professional.
5.3 - Starting set-up
For optimal set-up, make sure that all
the required accessories (room control,
decoupling kit, etc...) are connected before
starting the set-up. For room thermostats, make
sure they are in heating demand (sending a
closed contact to the pilot).
N
OTE
:
If you choose not to start set-up (NO) this option remains accessible
in the expert menu, by the
COMMISSIO
. sub-menu.
Inspect the entirety of the hydraulic connections (nuts with washers,
toric joints or anything assembled with glue) which may loosen
during transport or during the installation process, and tighten if
necessary.
After pressurising the appliance, it is important to check the
watertightness (both visually and by any lowering of pressure) of
all internal and external connections.
Any deterioration of the appliance due
to a lack of watertightness renders the
warranty null and void.
5.2 - Check watertightness
5.4 - Step 1: Circuit choice
Select the kind of circuit connected (domestic hot water,
radiators).
N
OTE
: Circuits are proposed according to the sensors which are
connected.
Activate the backfl ow prevention device of the installation to fi ll the
heating circuit to just over 1.5 bars of pressure.
The
PRIMO Pilot
automatically confi rms the fi lling of the installation
once the pressure reaches 1.6 bars.
A manual confi rmation (press
) is possible starting at 0.6
bars of pressure.
During the fi lling stage, the
PRIMO Pilot
indicates the pressure measured in the
heating circuit.
Filling
5.5 - Step 2: Filling
When the
PRIMO Pilot
is turned on for the fi rst time, it will ask you
to confi rm the language of use (French, English, German, Italian,
Spanish, or Polish), and will request to start set-up:
Choose
yes
and confi rm by pressing
.
COMMISSIO.