14
Technical Data
Type: dHE
Testing and certification:
Explosion category: CE0408
II 2 G EEx dem IIC T6
EC type examination certificate PTB 03 ATEX 1232
Housing degree of protection:
IP 66 IEC 60529
Insulation class
II
Time to wait before opening the device
≥
15 minutes
after turning off operating power
Housing:
Housing material
Plastic
Metal components
Stainless steel V4A (ASTM 316)
Dimensions
~
∅
278 x 365 mm
Weight
~ 5.9kg
Electrical connections: AC-version
DC-version
Mains connection (terminals 1 - 2)
L1, N
L+, L-
- Operating voltage U
B
85 – 265VAC
21.6 - 75VDC
- Operating frequency
50 – 60Hz
---
- Power consumption P
≤
12.5W
1)
≤
2.5W
1)
(Tone1B, Max. sound pressure)
- Power consumption (mute)
≤
2,5W
≤
2.5W
- Power factor cos(
ϕ
) 0.5
–0,7
2)
---
Control inputs (terminals 3 - 4 / 4 - 5)
all versions
- Open circuit voltage U
O
≤
5.5V
- Short circuit current I
O
≤
0.6mA
- Number of sounders connected in parallel
≤
32
- Wiring length
≤
3000m Minimum cross-section 0.75 mm
2
1)
Power consumption is, to a great extent, independent of the operating voltage. It does,
however, depend on the signalling tone and the sound pressure level. The given value specifies
the highest power consumption of the device.
2)
The power factor of the alternating current version depends on the operating voltage. The
following formula determines the operating voltage dependent operating current I
B
of the device.
(
)
B
3
B
B
U
10
11
,
1
794
,
0
U
P
I
∗
∗
−
∗
≈
−
For the DC version the following is valid: I
B
= P / U
B
Dimensions
365 mm
278 m
m