5.3 - Starting set-up
N
OTE
: If you choose not to start set-up (
NO
) this option remains
accessible in the expert menu, by the
COMMISSIO
. sub-menu.
When the
Pilot
is turned on for the fi rst time, it will ask you to confi rm
the language of use (French, English, German, Italian, Spanish, or
Polish), and will request to start set-up:
Choose
yes
and confi rm by pressing
.
COMMISSIO.
Activate the backfl ow prevention device of the installation to fi ll the
heating circuit to just over 1.5 bars of pressure.
The
Pilot
automatically confi rms the fi lling of the installation once
the pressure reaches 1.6 bars.
A manual confi rmation (press
) is possible starting at 0.6
bars of pressure.
5.5 - Step 2: Filling
During the filling stage, the
Pilot
indicates the pressure measured in the
heating circuit.
Filling
The
Pilot
will indicate when set-up has been achieved:
And will automatically put itself in standby mode.
The
Pilot
can be left in this state until fi rst use.
5.8 - Step 5: Finishing set-up
5.9 - First use
To turn on the
Pilot
, press
.
Long pressing
puts the
Pilot
in standby mode.
The purging cycle is launched for a duration of 30 minutes and will
automatically stop after that time is up.
At any time during the cycle, you can:
- Interrupt (or resume) the cycle by pressing on
.
- End the cycle and continue to the next step by pressing
5.6 - Step 3: Purging the installation
During the cycle, check that the automatic purgers are open and
regularly activate the manual purgers.
If the pressure in the circuit becomes insuffi
cient due to the volume
of air purged, the
Pilot
will indicate it and will pause the purging
cycle.
Activate the backfl ow prevention device or the fi lling valve to raise
the pressure. The purging cycle will resume automatically once there
is suffi
cient pressure.
During the purging cycle, the screen
indicates the countdown until the
automatic stop of the cycle as well as
the pressure in the circuit.
The purging cycle activates the circulator pump at an alternating
rhythm to allow the displacement and purging of any air bubbles
accumulated at high points of the installation using the
Pilot’s
automatic purger.
5.7 - Step 4 : Choosing the back-up
It is possible to select the electrical back-up, or not to declare a
back-up.
AIR BLEED
5.4 - Step 1: Circuit choice
Select the kind of circuit connected
(domestic hot water, radiators).
N
OTE
:
Circuits are proposed according to the connected sensors.