Master configuration
Import the latest GSDML file into your Master configuration tool. This file is available
from your supplier.
If your Master uses on-screen icons, two graphic bitmap files are available from the
website. SSPM_N.bmp indicates normal mode. SSPM_D.bmp indicates diagnostic
mode.
5.
Ground fault protection
NOTE
Ground fault protection is only available on ground fault enabled cards,
with soft starters running a compatible version of software. Contact your
supplier for assistance.
5.1
Overview
Ground fault protection
The Profinet Card can detect ground current and trip before the equipment is
damaged.
Ground fault protection requires a 1000:1 or 2000:1 5 VA current transformer (not
supplied). The soft starter can be configured to trip at 1 A~50 A. If ground fault current
rises above 50 A, the soft starter will trip immediately.
5.2
Connect the CT to the ground fault inputs
To use ground fault protection, a common mode current transformer (CT) must be
installed around all three phases. Use a 1000:1 or 2000:1 CT with rating of 5 VA and set
parameter 40E
Ground Fault CT Ratio
to match. Connect the CT to the ground fault
terminals (G1, G2, G3).
For maximum protection, the CT should be installed on the input side of the soft
starter.
5.3
Configure ground fault protection settings
Ground fault protection settings must be set in the soft starter.
Parameter Parameter name
Description
40A
Ground fault trip
level
Sets the trip point for ground fault current
protection.
40B
Ground fault trip
delay
Slows the soft starter’s response to ground fault,
avoiding trips due to momentary fluctuations.
40C
Ground fault trip
active
Selects when a ground fault trip can occur.