ADJUSTMENTS
Page 6
CSXi
710-02408-00H
Soft Stop Time
Select the soft stop ramp time (D).
Soft stop extends the time soft starter takes to
reduce voltage to zero.
The ramp time does not control the time the
motor will take to stop completely.
V
ol
ta
ge
Time
Excess Start Time
Configure the soft starter's excess start time
protection.
Select a time slightly longer than the motor
requires for a normal healthy start. The soft
starter will trip if the start does not complete
within the selected time (E).
Cur
ren
t
Time
Auxiliary Relay Function
Select the function of the soft starter's
programmable output (terminals 23, 24).
When set to "Run", the relay will operate when
the soft start is complete. When set to "Trip",
the relay will operate when the soft starter trips.
Time
Phase Sequence Protection
Configure the soft starter's phase sequence
protection.
Select the allowable phase sequences. A setting
of "Fwd" allows forward sequence (positive
rotation) only and a setting of "Any" defeats the
protection.
NOTE
Auxiliary relay function and phase rotation are configured using a shared switch. Set the
auxiliary relay function as required, then set phase rotation protection.