MECHANICAL INSTALLATION
Page 2
CSXi
710-02408-00H
2.1
Dimensions and Weights
A
B
C
D
E
F
G
H
Weight
Model
mm
(inch)
mm
(inch)
mm
(inch)
mm
(inch)
mm
(inch)
mm
(inch)
mm
(inch)
mm
(inch)
kg
(lb)
CSXi-007
CSXi-015
CSXi-018
98
82
201
188
165
55
90.5
23
2.2
CSXi-022
(3.85)
(3.22)
(7.91)
(7.40)
(6.49)
(2.16)
(3.6)
(0.9)
(4.85)
CSXi-030
CSXi-037
CSXi-045
145
124
215
196
193
-
110.5
37
4.0
CSXi-055
(5.70)
(4.88)
(8.46)
(7.71)
(7.59)
(4.4)
(1.5)
(8.81)
CSXi-075
CSXi-090
200
160
240
216
214
-
114.5
51
6.5
CSXi-110
(7.87)
(6.29)
(9.44)
(8.50)
(8.42)
(4.5)
(2.0)
(14.33)
2.2
Physical Installation
CSXi-007 ~ CSXi-055: Allow 100 mm (3.9 inch) between soft starters.
CSXi-075 ~ CSXi-110: Allow 200 mm (7.9 inch) between soft starters.
CSXi-007 ~ CSXi-055: Allow 50 mm (2.0 inch) between the soft starter and solid surfaces.
CSXi-075 ~ CSXi-110: Allow 200 mm (7.9 inch) between the soft starter and solid surfaces.
Soft starters may be mounted side by side with no clearance (that is, if mounted without
communications modules).
The soft starter may be mounted on its side. Derate the soft starter's rated current by 15%.
2