2. There are two Set Points -- CSP and HSP. Each Set Point has its 
own  output  relay,  Cooling  Relay  and  Heating  Relay.  Each  Set  Point 
has a control differential value, CdF or HdF. 

3.  In  the  Reverse  Logic  mode,  user  can  choose  to  use  either  the 
Cooling Relay (output socket on the left) or the Heating Relay (output 
socket on the right) to drive an external load. 

4.  In  the  Reverse  Logic  mode,  the  relay  will  be  energized  when  the 
probe reading is within the temperature range set by CSP (75° F) and 
HSP (32° F) as well as their differential bands CdF and HdF. 

Note  8. 

rST

 

is the factory reset parameter. Choose “Yes” to reset all 

the parameters back to factory settings.  

Note 9.

 PSd is the device access password (only available to TD120-

W  model).  This  parameter  is  used  to  lock  the  access  to  parameter 
settings on Aubersmart App.

 

 

7. How to install the sensor to the unit. 

The connector of sensor contains a slot for fitting pin connection. It also 
has a spring lock to prevent disconnections from accidental pulling on 

the cable. To install the sensor to the controller: 1) identify the key on 
the male connector (Figure 5, a) and the notch on the female connector 

(Figure 5, b); 2) hold the tail of the female connector, align the notch 
and the key, and push the female connector forward (Figure 5, c).  To 
remove  the  connector,  hold  the  spring-loaded  collar  on  the  female 
connector and pull it back. Please see Figure 6. 

 

(a) 

 

(b) 

 

(c) 

Figure 5. Install the sensor. 

 
 

 

Figure 6. Remove the sensor. 

 

 

 

 

 

 

 

 

 

 

 

 

Auber Instruments Inc. 

5755 North Point Parkway, Suite 99, 

Alpharetta, GA 30022 

www.auberins.com 

E-mail: [email protected] Tel: 770-569-8420 

 

Copyright 2007-2019, Auber Instruments All Rights Reserved. 

No part of this manual shall be copied, reproduced, or transmitted in any way 

without the prior, written consent of Auber Instruments. Auber Instruments 

retains the exclusive rights to all information included in this document. 

 

Содержание TD120-W

Страница 1: ...note 7 on page 3 2 Specification Temperature Control Range 50 105 C 58 221 F Temperature Resolution 0 1 C between 9 9 99 C 1 C between 50 10 C 100 120 C 0 1 F between 9 9 99 9 F 1 F between 58 10 F 100 248 F Temperature Accuracy 0 5 C or 0 9 F Temperature Control Mode On Off Control Heating and Cooling Temperature Control Output 10A 120V or 240V AC Audio Alarm High and Low Limit Sensor Type Silico...

Страница 2: ...Symbol Description Setting range Initial Note Menu for set points Figure 2 CSP CSP Cooling Set Point 58 248ºF 50 125ºC 67 0 1 HSP HSP Heating Set Point 58 CSPºF 50 CSPºC 62 0 Menu for parameters Figure 3 AH AH Alarm High Limit 58 248ºF 50 125ºC 95 0 2 AL AL Alarm Low Limit 58 AHºF 50 AHºC 34 CdF CDF Cooling Differential 0 50 0ºF 3 0 1 HdF HDF Heating Differential 0 50 0ºF 0 0 AS AS Cooling Antisho...

Страница 3: ...erature if the unit displays 37ºF when the actual temperature is 32ºF setting parameter oFS 5 will make the controller display 32ºF Note 6 C F determines the temperature unit It can be set to C Celsius C or F Fahrenheit F Note 7 LGC Control Logic advanced feature This parameter is used to change the current control logic mode Three modes are available NOR normal control logic default R C reverse l...

Страница 4: ...7 How to install the sensor to the unit The connector of sensor contains a slot for fitting pin connection It also has a spring lock to prevent disconnections from accidental pulling on the cable To install the sensor to the controller 1 identify the key on the male connector Figure 5 a and the notch on the female connector Figure 5 b 2 hold the tail of the female connector align the notch and the...

Отзывы: