background image

         AUBER INSTRUMENTS

  

 

 

 

 

 

 

 

         

WWW.AUBERINS.COM  

 

 

         2019.08                                                                    

   

                                                       P2/4 

 

 6 8

.

9

5 sec

SET

 AH

SET

 AL

SET

 CDF

SET

 HDF

SET

 6 8

.

9

Alarm High Limit

Alarm Low Limit

Cooling Differential

Heating Differential

Measured 

Temperature

  

Figure 3. Flow Chart Part 2

 

6. Parameter Settings 

To  change  the  target  temperature  (set  points),  press  SET  key 

momentarily.  The  controller  will  show  CSP  (Cooling  set  point),  press 
SET  again  will  show  HSP  (heating  set  point).  When  the  controller 
shows CSP or HSP, use Up or Down key to change the value. Then 
press SET key to confirm the change. See figure 2 for details  

To change the system parameters, press SET key for 5 seconds, the 
controller will enter the parameter set up mode. The first parameter AH 

will show on the display. Use Up or Down key to modify the parameter 
value.  Then  press  SET  key  to  confirm  the  change.  The  display  will 
show  the  parameter  again.  Press  the  SET  key  to  show  the  next 

parameter. The instrument will automatically exit if no key is pressed 
for 10 seconds.  See figure 3 & table 1 for details. 

Note  1.

  For  cooling  (or  heating),  the  output  will  be  off  when  the 

temperature is below (or over) the set point; will be on again when the 
temperature rises up (or drops down) to CSP + CdF (or HSP - HdF). 

The maximum value of the HSP can be set is the current value of CSP. 
But CSP can be set to the value between -58 ~ 248ºF or -50 ~ 125ºC. 

When the CSP is set to a value lower than current HSP, the HSP will 
be adjusted to the CSP value automatically. 

For example, when CSP = 67.0ºF, HSP = 62ºF, HSP can be set to any 
value  between  -58ºF  and  67.0ºF.  For  CSP,  it  can  still  be  set  to  any 

value between -58ºF and 248ºF. If you set it to 55.0, the HSP will be 
adjusted to 55.0ºF automatically. 

Small  differential  gives  tight  control;  large  differential  reduces  the 

frequency  of  cycle  on  and  off.  It  will  extend  the  life  of  relay  and 
compressor. 

Table 1. Parameters Description 

Code  Symbol 

Description 

Setting range  Initial  Note 

Menu for set points (Figure 2) 

CSP 

CSP 

Cooling Set Point 

-58 ~ 248ºF 

-50 ~ 125ºC 

67.0 

HSP 

HSP 

Heating Set Point 

-58 ~ CSPºF 

-50 ~ CSPºC 

62.0 

 

Menu for parameters (Figure 3) 

AH 

AH 

Alarm High Limit 

-58 ~ 248ºF 

-50 ~ 125ºC 

95.0 

AL 

AL 

Alarm Low Limit 

-58 ~ AHºF 

-50 ~ AHºC 

34 

 

CdF 

CDF 

Cooling Differential 

0 ~ 50.0ºF 

3.0 

HdF 

HDF 

Heating Differential 

0 ~ 50.0ºF 

0.0 

 

AS 

AS 

Cooling Antishort 

0 ~ 12 min 

SFA 

SFA 

Sensor Failure 

Operation 

0-0, 0-1, 1-0 

0-0 

oFS 

OFS 

Temperature Offset 

0 ~ 10.0 

C-F 

C-F 

Temperature Unit 

C: Celsius 

F: Fahrenheit 

LGC 

lgc 

Logic Control 

nor, r-C, r-H 

nor 

rST 

rst 

Factory Reset 

no, YES 

No 

PSd 

psd 

Device Access 

Password 

000~777 

777 

 

Note  2.

 When the measured temperature is higher than AH, the high 

limit alarm will be on; when the measured temperature is lower than AL, 
the low limit alarm will be on. 

When alarm is on, the display will be flashing between the measured 

value and alarm type. To mute the alarm when it is on, press the Down 
key momentarily. If the measured value gets out of the alarm zone then 
gets  back  to  the  alarm  zone  again,  the  alarm  will  be  on  again.  To 
disable the alarm, set AH the same value as AL (AH = AL). 

The maximum value of the AL can be set is the current value of AH. 
But AH can be set to the value between -58 ~ 248ºF or -50 ~ 125ºC. 
When  AH  is  set  to  a  value  lower  than  current  AL,  the  AL  will  be 
adjusted to the AH value automatically.

 

For example, when AH = 95.0ºF, AL = 32ºF, AL can be set to any value 
between -58ºF and 95.0ºF. For AH, it can be set to any value between 

-58ºF  and  248ºF.  If  you  set  it  to  25.0ºF,  the  AL  will  be  adjusted  to 
25.0ºF automatically. 

Note 3. 

The Cooling Anti-short is the delay time to turn the cooling load 

on. 

W

hen the controller is used for cooling and load is a compressor, it 

should not turn on the compressor when it is at high pressure (just right 

after it turned off). Otherwise, it may shorten the life of the compressor. 
The  Anti-short  cycle  delay  function  can  be  used  to  prevent  the  rapid 

cycling of the compressor. It establishes the minimum time that the NO 

Содержание TD120-W

Страница 1: ...note 7 on page 3 2 Specification Temperature Control Range 50 105 C 58 221 F Temperature Resolution 0 1 C between 9 9 99 C 1 C between 50 10 C 100 120 C 0 1 F between 9 9 99 9 F 1 F between 58 10 F 100 248 F Temperature Accuracy 0 5 C or 0 9 F Temperature Control Mode On Off Control Heating and Cooling Temperature Control Output 10A 120V or 240V AC Audio Alarm High and Low Limit Sensor Type Silico...

Страница 2: ...Symbol Description Setting range Initial Note Menu for set points Figure 2 CSP CSP Cooling Set Point 58 248ºF 50 125ºC 67 0 1 HSP HSP Heating Set Point 58 CSPºF 50 CSPºC 62 0 Menu for parameters Figure 3 AH AH Alarm High Limit 58 248ºF 50 125ºC 95 0 2 AL AL Alarm Low Limit 58 AHºF 50 AHºC 34 CdF CDF Cooling Differential 0 50 0ºF 3 0 1 HdF HDF Heating Differential 0 50 0ºF 0 0 AS AS Cooling Antisho...

Страница 3: ...erature if the unit displays 37ºF when the actual temperature is 32ºF setting parameter oFS 5 will make the controller display 32ºF Note 6 C F determines the temperature unit It can be set to C Celsius C or F Fahrenheit F Note 7 LGC Control Logic advanced feature This parameter is used to change the current control logic mode Three modes are available NOR normal control logic default R C reverse l...

Страница 4: ...7 How to install the sensor to the unit The connector of sensor contains a slot for fitting pin connection It also has a spring lock to prevent disconnections from accidental pulling on the cable To install the sensor to the controller 1 identify the key on the male connector Figure 5 a and the notch on the female connector Figure 5 b 2 hold the tail of the female connector align the notch and the...

Отзывы: