contact remains open (after reaching cutout) before closing again. The 
delay overrides any Load Demand and does not allow the NO contacts 
to  close  until  the  set  time-delay  value  has  elapsed.  It  gives  time  to 
release the refrigerant pressure through evaporator. It is typically set to 
4 ~ 6 minutes. 

Note 4. 

The SFA defines how the output would be if the sensor fails. It 

can be set to 0-0, 0-1 or 1-0. Please refer to table 2 for details. 

Table 2. Output of the controller when sensor fails:

 

SFA  Controller output when sensor fails 

0-0 

cooler off, heater off 

1-0 

cooler on, heater off 

0-1 

cooler off, heater on 

 
For  example,  when  the  unit  controls  a  refrigerator  for  food,  you  may 

want  to  set  the  SFA  to  ON  if  the  sensor  fails  to  keep  the  food  cold. 
When it controls a heater, you may want to set the output to OFF for 
safety purpose.

 

Note  5. 

The  offset  is  used  to  set  an  input  offset  to  compensate  the 

error produced by the sensor or input signal itself. 

For example, for temperature, if the unit displays 37ºF when the actual 
temperature  is  32ºF,  setting  parameter  oFS  =  -5  will  make  the 
controller display 32ºF. 

Note  6. 

C-F  determines  the  temperature  unit.  It  can  be  set  to  C 

(Celsius, ˚C) or F (Fahrenheit, ˚F).

 

Note 7.

 LGC Control Logic (advanced feature). This parameter is used 

to change the current control logic mode. Three modes are available:  

 

 NOR -- normal control logic (default) 

 R-C -- reverse logic, output send to Cooling socket (left) 

 R-H -- reverse logic, output send to Heating socket (right) 

If set to default mode (NOR), when this controller is calling for heat, the 
heating output socket on the right will be triggered. When this controller 
is calling for cool, the cooling output socket on the left will be triggered.  

If  set  to  reverse  modes  (R-C/R-H),  when  this  controller  is  calling  for 

heat or cool, the output is disabled. In other conditions, the output will 
be  triggered.  You  can  assign  this  output  to  cooling  socket  (R-C),  or 
heating socket (R-H). For details, see flow chart below.  

 

Figure 4. Reverse mode flow chart. 

Explanation:  

1. The plot on the top shows how the room temperature changes as 
time  goes  by.  The  diagram  on  the  bottom  shows  the  status  of  the 
output relay as temperature move across each set point. 

Содержание TD120-W

Страница 1: ...note 7 on page 3 2 Specification Temperature Control Range 50 105 C 58 221 F Temperature Resolution 0 1 C between 9 9 99 C 1 C between 50 10 C 100 120 C 0 1 F between 9 9 99 9 F 1 F between 58 10 F 100 248 F Temperature Accuracy 0 5 C or 0 9 F Temperature Control Mode On Off Control Heating and Cooling Temperature Control Output 10A 120V or 240V AC Audio Alarm High and Low Limit Sensor Type Silico...

Страница 2: ...Symbol Description Setting range Initial Note Menu for set points Figure 2 CSP CSP Cooling Set Point 58 248ºF 50 125ºC 67 0 1 HSP HSP Heating Set Point 58 CSPºF 50 CSPºC 62 0 Menu for parameters Figure 3 AH AH Alarm High Limit 58 248ºF 50 125ºC 95 0 2 AL AL Alarm Low Limit 58 AHºF 50 AHºC 34 CdF CDF Cooling Differential 0 50 0ºF 3 0 1 HdF HDF Heating Differential 0 50 0ºF 0 0 AS AS Cooling Antisho...

Страница 3: ...erature if the unit displays 37ºF when the actual temperature is 32ºF setting parameter oFS 5 will make the controller display 32ºF Note 6 C F determines the temperature unit It can be set to C Celsius C or F Fahrenheit F Note 7 LGC Control Logic advanced feature This parameter is used to change the current control logic mode Three modes are available NOR normal control logic default R C reverse l...

Страница 4: ...7 How to install the sensor to the unit The connector of sensor contains a slot for fitting pin connection It also has a spring lock to prevent disconnections from accidental pulling on the cable To install the sensor to the controller 1 identify the key on the male connector Figure 5 a and the notch on the female connector Figure 5 b 2 hold the tail of the female connector align the notch and the...

Отзывы: