function is rising-edge triggered. The logic signal should normally be at high 
level. The function starts when the signal goes from low to high. If you have an 
inverted logic signal, you need to connect a NPN transistor between terminal 
and COM; add 10Kohm resistor to the gate for signal input.

 See Figure 6.  

7. Terminal 2 is reserved for customized applications.  
 

Note for terminal 3, 4, and 5.

 The function of all these terminals is 

accomplished by the rising phase of control signal. If the control signal is from 
a momentary NO switch that is connected to the terminal, the action starts 
when switch is released (from close to open). When the control signal is from 
another digital device, the action starts when voltage goes from low to high.  
 

5. How to Set the Timer and Relay Delay Time T1/T2 

Press “SET” key momentarily, T1 will show up at the top display. Use Up and 

Down key to set the value. Press SET again to set the T2 (only for delayed 
interval or cycle mode). Press SET key confirm the setting and exit the timer 
setting mode.  
 
When adjusting the time, each time the Up or Down key is pressed, the value 
will increase by one unit. But if you press and hold it, the value will continuously 
increase, as the holding time increases, the speed of number increasing will 
accelerate. You can use this feature for large number increment. When the 
number is getting close to desired value, release the key. Then, press it 
momentarily for fine setting adjustment.    
 

6. Programming 

Press SET key for 3 seconds to enter programming mode. For each parameter 
setting, use up/down key to select different programming values. Press SET 
key to confirm and move on to next parameter. See Figure 3 for the procedure. 
For the definition of each programming value, see following section. 

 

0000

0000

Process Value
Set Value

SET

OUT

OFDL

OUT
OFDL

tdir
dn

SET

FUNC

SDL

RUN

RST

Func
SdL

RUN
rSt

SET

SET

3s

SET

T1

S

T2

S

tdir

dn

T1
S

T2
S

SET

 

Figure 3. Flow chart of how to program JSL-74. 

Definition of Programming Values 
Func

, timer operating function mode.     

SdL

 (single delay): relay turns on at the beginning of relay delay time T1 

(OFDL); relay turns on at the end of relay delay time T1 (ONDL). It will not 
change until the timer is reset or repowered again. In Single Delay ON mode, a 
special parameter for stop function, STOP will show up in the parameter menu. 
For details please refer to note1 below. 

dint

 (delayed interval): relay turns on at the end of T1 time delay then off at the 

end of T2 time delay (OFDL); relay turns off at the end of T1 time delay then on 
at the end of T2 time delay (ONDL). There is no repeat. 

CYCL

 (cycle): repeat relay on and off in cycle. Relay turns on at the end of T1 

time delay then off at the end of T2 time delay (OFDL); relay turns off at the 
end of T1 time delay then on at the end of T2 time delay (ONDL). It will repeat 
this cycle until power is off. 
 

T1 or T2

, timer range.   

S

: 0.01 s ~ 99.99 s.   

M:S

: 1 s ~ 99 m 59 s. 

M

: 1 m ~ 9999 m. 

H:M

: 1 m ~ 99 h 59 m. 

 

tdir

, timing direction.  

up

: counting up. 

dn

: counting down. 

 

OUT

, relay output mode. 

OFDL

 (off delay): relay will be on at the start of timer and off when time reach 

the set point. 

ONDL

 (on delay): relay will stay off at the start of timer and on when time reach 

the set. 
 

RUN

, timer starting run mode.    

PU

 (power up): timer starts when powered up.  

rSt

 (reset): timer starts when reset button is pressed and released 

 

 

 

 

 

Note 1

: Running the single delayed on mode. 

When running the Single Delay On mode, depending on the applications, user 
may want the relay to stay at off (initial state), or, stay on (final state) when the 
operation is interrupted by stop function. Here are two examples. A) Some user 
uses the timer to turn on a buzzer at the end of a process for notification 
purpose. He wants to be able to disable the buzzer (change to initial state) by 
simply pushing a button once he acknowledged the notification. B) Some user 
wants to delay the process of turning on an oven. But sometimes, he may want 
to cancel the delay (change to the final state) to start the oven by pushing the 
stop key.  In order to satisfy these two conflict requirements, a special 
parameter for stop function, STOP will show up in the parameter menu when 
both ONDL (on delay) and SDL (single delay) are selected, STOP can be 
selected as 0 (default) or 1. When it is set to 0, during the delay, stop signal will 
set relay to the final state (pulled-in). When it is set to 1, during the delay, stop 
signal will set the relay to the initial state (dropped-out). When the time delay is 
finished and relay pulled in, user can reset the relay to the initial state by 
sending a stop signal, regardless of the STOP setting.   
 

 

  
 
 