background image

NOVUS AUTOMATION 

1/5 

 

 

 

NT240 TIMER 

PROGRAMMABLE TIMER – INSTRUCTIONS MANUAL V20x D 

INTRODUCTION 

The NT240 is a programmable timer designed to monitor time 

intervals, activating its outputs according to some predefined mode of 

operation and time intervals chosen by the user.  The user can also 

create its own mode of operation to best fit his application.  
The timer shows the elapsed time in an increasing or decreasing 

mode, with resolutions from 0.01 s to 1 hour. 
Digital inputs are available to perform specific functions.  Standard 

outputs are relay and logic pulse (5 V) types.  

SPECIFICATIONS 

Input types:  - NPN/PNP sensors  

   

  - NO/NC dry contact 

   

  - Voltage:  Logic level 1:  5 to 30 Vdc 

   

     

  Logic level 0:  -0.5 to 0.5 Vdc 

Output:  - 1 SPST Relay 3 A / 250 Vac (3 A / 30 Vdc) 

- 1 voltage pulse 5 V / 25 mA 

Time delay after turning on the timer: 200 ms 
Accuracy: 0,1 % of displayed time 
Response time: 10 ms for the relay output and 0.3ms for the pulse 

output 
Auxiliary voltage source: 12 Vdc  ±10 % / 50 mA 
Power: 100 to 240 Vac/dc (±10 %), 50/60 Hz or optional 24 V: 12 to 

24 Vdc / 24 Vac (-10 % / 20 %) 
Maximum consumption: 3 VA 
Operating environment: 0 to 55 ºC, Relative humidity (maximum): 80 % 

up to 30 ºC. For temperatures above 30 ºC, decrease 3 % per ºC. 
Dimensions: 48 x 48 x 106 mm 
Cut for panel fixation: 45.5 to 45.5 mm 
Approximate weight: 150 g 

TIMER INPUTS 

The timer has three control inputs: START, HOLD and RESET.  
These inputs can be configured to accept four different electrical 

(logical) signals (see parameter 

PnP

 in the configuration). The signal 

type there defined becomes the same for all three inputs. 
START: Starts time counting 
The start input, when activated, starts the temporization cycle, using 

the operating mode selected in the configuration. The START input is 

available on terminals 9 and 12. 
HOLD: Interrupts time counting 
The HOLD input, while active, interrupts time counting. When the 

HOLD input is released, the time counting resumes from the point it 

was interrupted.  
NOTE:  The HOLD function can activated by the 

F

  key, when 

programmed to perform as such on the 

F

 

Fv

 parameter of the timer. 

Using the 

F

  key as the input to HOLD function, pressing once 

stops the timer and pressing again resumes the counting of time. 
RESET: Timer Input Reset 
The Reset input, when activated, cancels the current temporization 

and returns the timer display to the initial value. While Reset is 

active, the temporization can not be started. When Reset is released, 

the timer becomes available for new temporization.  

TIMER OUTPUTS 

The timer provides an output, called TIMER OUTPUT, which can be 

activated in various ways according to the selected temporization 

mode. This output is available as a relay contact and as a voltage 

pulse (both operate simultaneously).  
Output types: 1 SPST – 3 A / 250 Vac relay, terminal 3 and 4; 
   

    1 voltage pulse of 5 V / 25 mA, terminals 5 and 6 

Output delay time:  10 ms for relay output; 
   

     

0.3 ms for pulse output. 

The 

0Per

 parameter defines the way the output will operate. 

 

AUXILARY SUPPLY OUTPUT 

A 12 Vdc 

±

10 % (50 mA max) auxiliary power supply is provided on 

terminals 7 and 8 to power electronic sensors used as inputs to the 

timer. The (-) supply terminal is wired internally to the GND terminal 

of the inputs (the supply is not electrically isolated from the 

inputs). 

 

INSTALLATION 

Panel Mounting  
Insert the unit into the panel cut-out (use the dimensions specified in 

the "Technical Specifications" section) and slide the mounting clamp 

from the rear to a firm grip at the panel.  
The timer circuitry can removed from its case from the front, without 

the need of disassembling the instrument from the panel, leaving the 

wire connections intact.  
 
Electric connections 
Figure 01
 shows the timer terminals along with theirs functions. 

 

Figure 01 – Timer connections panel 

Recommendations for Installation  

 

Input signal wires should be laid out away from power lines and 

preferably inside grounded conduits. 

 

Instrument mains should be suitable for this purpose and wires 

should not be shared with high consumption motors and inductors. 

 

Use of RC filters (47 

 and 100 nF) in parallel with solenoids and 

contactor coils are highly recommended.  

 

In monitoring and control applications it is essential to consider 

what can happen when any part of the system is subject to failure.  

 

Отзывы: