Installation & Operation Manual
L932/B
Installation & Operation Manual Ver.1.1
The following chart shows main technical parameters of Model L932/B
Intelligent Pump Controller
.2.
Trip response time of over load
Trip response time of open phase
AC220V-AC440V /60HZ Three Phase
refer to the nameplate
Rated input voltage
5sec-5min
<
2sec
Trip response time of short circuit
Trip response time of under / over voltage
Trip response time of dry run
Recovery time of over load
Recovery time of under / over voltage
Recovery time of dry run
Trip voltage of over voltage
Trip voltage of under voltage
Liquid level transfer distance
<
0.1sec
<
5sec
6sec
30min
5min
30min
115% of the rated input voltage
80% of the rated input voltage
≤
1000m
Dry run
Over load
Transient surge
Under voltage
Over voltage
Pump shaft rust protection
Protection function
Working temperature
Working humidity
Degree of protection
Install position
Unit dimensions ( L x W x H)
Unit weight (net)
Main installation data
-25
℃
-- +55
℃
20% - 90%RH
IP54
Horizontal
31 x 22x 12cm
3.6kg
RS485 technical data
Baud rate
1200 bps
、
2400 bps
、
4800 bps
、
9600bps
Default: 9600bps
RS485 Bus Interface: asynchronism semiduplex
Physics Interface
Protocol type
MODBUS Protocol (RTU)
Pump stalled
Short circuit
Three phase unbalance
Phase reversal
Repeated start
Open phase
Manual / Auto
Pressure control characteristic
Main technical data
Control method
Rated output power
0.75-15KW (1HP-20HP)
refer to the nameplate
Main technical characteristic
Control characteristic
pressure control
Pressure transmitter with0
.
5
-
4
.
5V
analog
signal