Step 5CS –

 - Allows selection of one of the following 

using the 

V

or 

W

 buttons:

• the Control Valve to have no hard water bypass;
• the Control Valve to act as an alternator; or
• the Control Valve to have a separate source during the 
regeneration cycle.

Select OFF when none of these features are used.

Only use Clack No Hard Water Bypass Valves or 
Clack Motorized Alternating Valves (MAV) with these 

selections.  Clack No Hard Water Bypass Valves (1” or 1.25” V3070FF or V3070FM) are not designed to be used with the alternator or separate 
source functions.  The V3063 and V3063BSPT motorized alternating valves are not designed to be used as a no hard water bypass or separate 
source inlet if the pressure differential is more than 60 psi.

Con guring the Control Valve for No Hard Water Bypass Operation:

Select nHbP for control operation.  For no hard water bypass operation the three wire connector is not used. 

Selection requires that a connection to MAV or a Clack No Hard Water Bypass Valve is made to the two pin connector labeled ALTERNATOR 
DRIVE located on the printed circuit board. If using a MAV, the A port of the MAV must be plugged and the valve outlet connected to the B 
port.  When set to nHbP the MAV will be driven closed before the  rst regeneration cycle that is not FILL or SOFTENING or FILTERING, and 
be driven open after the last regeneration cycle that is not FILL.

NOTE: If the control valve enters into an error state during regeneration mode, the no hard water bypass valve will remain in its current state 
until the error is corrected and reset.

Con guring the Control Valve for Separate Source Operation:

Select nHbP for control operation.  For separate source operation the three wire connector is not used. 

Selection requires that a connection to a Clack Motorized Alternator Valve (MAV) is made to the two pin connector labeled ALTERNATOR 
DRIVE located on the printed circuit board. The C port of the MAV must be connected to the valve inlet and the A port connected to the separate 
source used during regeneration.  The B port must be connected to the feed water supply.

When set to nHbP the MAV will be driven closed before the  rst regeneration cycle, and be driven open after the last regeneration cycle.

NOTE: If the control valve enters into an error state during regeneration mode, the MAV will remain in its current state until the error is 
corrected and reset.

Selecting the Control Valve to act as an alternator:

Prior to starting the programming steps, connect the interconnect cable to each control valve board’s three pin connector labeled 

“INTERCONNECT”.  Also connect the meter cord to either control valve to the three pin connector labeled “METER”.

Valve Programming Steps

Con guration 

Settings

Step 3CS

Select Volume

Set Volume

Con guration 

Settings

Step 4CS

Set regeneration time option to “On O”.

Set regeneration time option to “On O”.

Con guration 

Settings

Step5CS

Set to ALTA

Connect ALTA valve to the MAV’s A 

port and connect the MAV’s two pin wire 

connector to the two pin connector labeled 

“DRIVE” on the ALTA valve

Set to ALTb

Connect ALTb valve to the MAV’s B port.  No 

connections between the ALTB valve and the MAV 

are made.

Installer Display 

Setting

Step 2I

Enter the Volumetric Capacity for the System

Enter the Volumetric Capacity for the System (the 

same as Valve A)

Installer Display 

Setting

Step 3I

Set Day Over ride to “oFF”

Set Day Over ride to “oFF”

NOTE: If the control valve is in an error state during regeneration mode the MAV will close the B port and keep open the A port until the error is 
corrected and reset.

For Clack Corporation alternator systems using the WS1, WS1.25, WS1.5 and WS2L valves the stand by tank will be periodically brought on 
line for a short time to keep its bed fresh.  The logic is that once a tank is in standby and the time has passed either 6 AM or 6 PM (18:00) at the 
next and all subsequent 6 AM and 6 PM times the stand by tank will be brought on line until 10 gallons (37.8 liters) has passed through it.  It 
will then be placed back on standby.

For Clack Corporation alternator systems using the WS2 valve, when NEXT is pressed after selecting ALTA or ALTb, a display will allow the 
user to set the amount of pre-service rinse time for the stand by tank just prior to returning to service. 

Press NEXT to go to Step 6CS. Press REGEN to return to previous step.

Step 5CS

Volume

Volume

Control Valve cont:

Содержание TTV1EEM-3T

Страница 1: ...www aquat com Installation Operation and Maintenance Manual CAUTION Read and Follow all safety rules and operating instructions before first use of product DEALER NAME DEALER PHONE MODEL SERIAL DATE...

Страница 2: ...Aqua Treatment Service 2013 www aquat com...

Страница 3: ...ons 5 User Displays 6 Configuration Settings 7 9 Setting Regeneration Cycle Times 10 Installer Display Settings 11 12 Diagnostics 13 Parts Breakdown System 14 Control Valve 15 23 Specifications 24 Tro...

Страница 4: ...stallation site of the equipment A drain must be available within 20 feet of the equipment Location of the equipment must be where it is not subject of freezing direct sunlight or room Temperature ove...

Страница 5: ...alling systems Sanitary Sewer Line Cold Water Inlet Cold Water Outlet Valve Control Clean Water Tank Assembly System Drain Line Floor Drain Hard Water Line to Unsoftened Fixtures Direction of water fl...

Страница 6: ...12V 1 V3186 01 WS1 AC ADAPTER CORD ONLY Not Shown V3178 WS1 Drive Back Plate 1 EE Front Cover and Drive Assembly 1 4 6 5 3 2 AC Adapter U S International Supply Voltage 120 V AC 230V AC Supply Freque...

Страница 7: ...edule a regeneration at the preset delayed regeneration time Pressing again and releasing will cancel the regeneration Pressing while in regeneration will advance to the next cycle Pressing in the pro...

Страница 8: ...0 User 5 Shows current time Setting Time of Day Push NEXT button until time of day screen is displayed Press and hold the V or W arrow until the SET indicator is displayed and the hour ashes Press the...

Страница 9: ...h 28 selected in Installer Display Settings If a meter is not used the total ow and ow rate user displays and the volume display in Diagnostics will be shown as 0 If 7 Volume gallons is selected the r...

Страница 10: ...the feed water supply When set to nHbP the MAV will be driven closed before the rst regeneration cycle and be driven open after the last regeneration cycle NOTE If the control valve enters into an err...

Страница 11: ...ed for an accumulative time of 2 minutes a regeneration will occur at the scheduled regeneration time HoLd If the dP switch is closed a regeneration will be prevented from occurring Not viewed if Step...

Страница 12: ...length of the second backwash from 1 20 minutes using the or buttons Press NEXT to go to Step 6CT Press REGEN to return to previous step Step 6CT Adjust the length of rinse from 1 20 minutes using the...

Страница 13: ...NEXT and V buttons simultaneously for ve seconds and release Step 2I Adjust days from 1 28 Press NEXT to go to Step 3I Press REGEN to exit Installer Display Step 3I Use V or W buttons to set time of...

Страница 14: ...evious display 7 Day or 7 Volume Gallons selected in Con guration Settings Step 3CS Step 1I To enter Installer Display press the NEXT and V buttons simultaneously for 5 seconds and release Step 2I Use...

Страница 15: ...curred Press NEXT to go to Step 3D Press REGEN to exit Diagnostics Step 3D Display shows the volume of water treated in gallons treated since the last regeneration If Volume gallons 28 Volume gallons...

Страница 16: ...Aqua Treatment Service 2013 www aquat com 14 Parts Breakdown...

Страница 17: ...Aqua Treatment Service 2013 www aquat com 15 Parts Breakdown cont...

Страница 18: ...WS1 Piston Down ow ASY 1 4b V3011 01 WS1 Piston Up ow ASY 5 V3174 WS1 Regenerant Piston 1 6 V3135 O ring 228 1 7 V3180 O ring 337 1 8 V3105 O ring 215 Distributor Tube 1 Not Shown V3001 WS1 Body ASY...

Страница 19: ...Aqua Treatment Service 2013 www aquat com 17 Parts Breakdown cont...

Страница 20: ...fill Port Plug Asy This part is required for backwash only systems 2 H4615 Elbow Locking Clip 1 3 JCP P 6 Polytube insert 3 8 1 4 JCPG 6PBLK Nut 3 8 1 5 H4613 Elbow Cap 3 8 1 6 V3163 0 ring 019 1 7 V3...

Страница 21: ...WS1 DLFC 1 0 gpm for V3162 013 WS1 DLFC 1 3 gpm for V3162 017 WS1 DLFC 1 7 gpm for V3162 022 WS1 DLFC 2 2 gpm for V3162 027 WS1 DLFC 2 7 gpm for V3162 032 WS1 DLFC 3 2 gpm for V3162 042 WS1 DLFC 4 2 g...

Страница 22: ...Aqua Treatment Service 2013 www aquat com 20 Parts Breakdown cont...

Страница 23: ...WS1 Split Ring 2 3 V3105 O Ring 215 2 4 V3189 WS1 Fitting 1 PVC Solvent 90 2 Order No V3007 02 Description WS1 Fitting 1 Brass Sweat Assembly Drawing No Order No Description Quantity 1 V3151 WS1 Nut...

Страница 24: ...V3007 08 DESCRIPTION WS1 FITTING 1 1 4 PLASTIC MALE BSPT ASSEMBLY Drawing No Order No Description Quantity 1 V3151 WS1 Nut 1 Quick Connect 2 2 V3150 WS1 Split Ring 2 3 V3105 O Ring 215 2 4 V3361 WS1 F...

Страница 25: ...tor 2 5 V3146 WS1 Bypass Cap 2 6 V3147 WS1 Bypass Handle 2 7 V3148 WS1 Bypass Rotor Seal Retainer 2 8 V3152 O ring 135 2 9 V3155 O ring 112 2 10 V3156 O ring 214 2 Not Shown Order No V3191 01 Descript...

Страница 26: ...000 32 000 108 TTV1EEM 5T 9 275 9 22 1 10 x 54 30 000 48 000 140 H1071 02 SALT GRID 60 33 NOTES Overall Depth of Unit 24 All Dimensions are of the Unit only Size will very depending on plumbing used f...

Страница 27: ...Board f Replace PC Board 4 Control valve regenerates at wrong time of day a Power outage a Reset time of day If PC Board has battery back up present the battery may be depleted See Front Cover and Dri...

Страница 28: ...Check for leaking xtures that may be exhausting capacity or system is undersized 10 Residual regenerant being delivered to service a Low water pressure a Check incoming water pressure water pressure...

Страница 29: ...t power supply from PC Board for 5 seconds and then reconnect c Missing reduction gears c Replace missing gears 15 E2 Err 1002 Err 102 Control valve motor ran too short and was unable to nd the next c...

Страница 30: ...function a Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC Board for 5 seconds and then reconnect Then re program valve to...

Страница 31: ...d or reaffixing any ATS part or component thereof or be liable for any injury loss or damage direct or indirect special or consequential arising out of the use of misuse or the inability to use such p...

Отзывы: