C Auto Mode 1
This sub menu can be used for Auto operation of
Relay 1. User can select relay 1 setting on auto mode
from this sub menu. This relay will operate based on
HI Setpoint and LO Setpoint values inserted by user.
When the analogue input value rises from HI setpoint
value, then Relay 1 will turn ON. When the analogue
input value falls from LO Setpoint value, then Relay 1
will turn OFF.
Pressing Enter button will turn ON/OFF this mode.
Menu Button Insert Password Downward Button Enter Button Relay 1
Setting
Enter Button Downward Button Auto Mode 1
D
HI Setpoint
User can select relay 1 high setpoint percentage value
between 0 to 100 % depending on the 4~20mA input
the level controller is receiving. This value should be
larger than LO setpoint otherwise controller will not
accept the value.
Menu Button Insert Password Downward
Button Enter Button Relay 1 Setting
Enter
Button Downward Button HI Setpoint
E
LO Setpoint
User can select relay 1 low setpoint percentage value
between 0 to 100 % depending on the 4~20mA input
the level controller is receiving. This value should be
less than LO setpoint otherwise controller will not
accept the value.
Menu Button Insert Password Downward
Button Enter Button Relay 1 Setting
Enter
Button Downward Button LO Setpoint
F
Invert Logic
User can invert the HI and LO setpoint logic for relay
1 using this option. This will invert the Auto Mode
logic for use whenever required. Before making it ON
user must ensure the setpoint values, span values for
Relay 1 and its corresponding channel.
Menu Button Insert Password Downward
Button Enter Button Relay 1 Setting
Enter
Button Downward Button Invert Logic