background image

 

 

 

 

Installation

 

 

 

AtmosAir Matterhorn series equipment can be mounted in a duct or air handler wall, using the 
faceplate mounting flange and its weather-strip gasket; or inside a plenum using a semi-custom 
mounting bracket.  The units operate best when located after all filters, coils, and fans.  Various 
mounting arrangements are possible; however, the available options may be limited due to size and 
configuration restrictions. 

When mounted on the side of a duct or air handler wall, the enclosure should not be exposed to 
direct sunlight or moisture.  If installing outside, a weatherproof enclosure with an access panel for 
servicing should be installed over the AtmosAir equipment. 

The AtmosAir Matterhorn series operates on 220~250 VAC, 50/60 Hz.  The tube and electrode 
contacts should not come into contact with any conductive surface.  A minimum 101.60mm 
clearance around the tube is recommended.  All exposed metal parts are grounded. 

 
 

 

Mechanical Installation

 

 

Carefully remove the equipment from its shipping container. Inspect the main components, gasket, 
and tube(s) for damage.  Verify that the 

unit’s voltage rating is the same as the available voltage, 

220~250 VAC. 

Install the ionization tube:  Gently pull the conductor strap back to allow the tube to turn freely; screw 
the end screw of the tube into the tube-holder hand-tight.  Do not over-tighten the tube!  Once the 
tube is secure, return the conductor strap to its normal position and ENSURE SOLID CONTACT IS 
MADE WITH THE TU

BE’S OUTER MESH. 

 

 

Location and Orientation: 

Install the unit downstream of filters, coils, and fans with tubes vertical 

whenever possible. If multiple units are installed in the same duct, stagger the units in the airflow 
so they are not in the same airflow path. 

 

For in-duct installation:  

Verify the flange gasket is in place and in good shape to ensure the unit 

seals properly.  Make a cut-out in the duct sized at 139.70mm high x 152.40mm wide.  A paper 
template is included for ease of installation; use the lines to cut the cut-out hole, then trace the cut-
out and mark the locations of the mounting holes for the Matterhorn series. 

 

 

Using the marked holes from the backer-plate template, affix the unit securely in the duct using self- 
tapping screws (if not using backer-plate).  Do not over-tighten, this may strip the screw-hole.  The 
unit is self-sealing to the duct so no further sealing is needed. 

Содержание Matterhorn Series

Страница 1: ...Installation Operations and Maintenance Guide Matterhorn Series...

Страница 2: ...negative ions into the air stream to be treated The number and size of the ionization tubes used is dependent upon the airflow size of the space and severity of the pollution and odors The AtmosAir M...

Страница 3: ...the unit s voltage rating is the same as the available voltage 220 250 VAC Install the ionization tube Gently pull the conductor strap back to allow the tube to turn freely screw the end screw of the...

Страница 4: ...d flat to duct wall to retain backer plate to secure the plate to the duct Attach the Matterhorn series system using the six 6 35mm screws The studs on the backer plate will secure the Matterhorn seri...

Страница 5: ...ctioning LED light may improperly indicate that the system is not functioning Be sure to disconnect from the mains power before performing maintenance or troubleshooting the system MaintenanceRequirem...

Страница 6: ...placed once every 24 months at a minimum as the production efficiency slowly declines over time due to the stress caused by plasma and lack of cleanliness of the electrodes Old or excessively dirty tu...

Страница 7: ...the power surge in the form of a visual or audio cue 4 It may be necessary to remove the tube s to ensure that the transformer is working properly in the absence of tubes If the fuse still blows then...

Страница 8: ...cing effectiveness or worse the seal between the dielectric material and the cap may break 6 Once the tube is secure return the conductor strap to its normal position and ensure solid contact is made...

Страница 9: ...the tube from the tube holder It is important to hold the tube only by the end cap not the core or mesh when first loosening the tube 6 Carefully remove the tube from the unit and release the conduct...

Страница 10: ...essor It may be useful to remove the tubes for improved cleaning Cleaning the general area around the tubes to remove dust dirt and debris will keep the tubes clean longer CAUTION Do not immerse the t...

Страница 11: ...ency and life of the tube The silicone seal between the tube and the cap keeps moisture from infiltrating the tube Excessive aluminum oxide build up on the inner electrode can decrease the strength of...