background image

 

 

 

 

Thorough Clean, continued

 

 
4. Clean the tube with a mild soap solution, and a soft cloth or sponge. A non-scratch scrub sponge 
may help remove sticky material. Clean any carbon tracking residue off of the end cap. Rinse or wipe 
the tube and dry thoroughly. Be sure to avoid the seal between the cap and tube and between the cap 
and the end screw when rinsing.

 

 
5. Once the mesh and tube are completely dry, replace the mesh on the tube by sliding it gently over 
the tube. Be sure that the outer mesh is at least 1.25 cm from the end cap, and that both vertical 
seams on the inner and outer electrodes line up. 

 
Once the tubes are clean and completely dry, reinstall the tubes in the system.  

 

Tips on Tube Life 

 

Cleaning the tube is beneficial because it reduces stress on the transformer and also removes any 
dirt or oil that can inhibit the plasma from forming on the outside of the tube. Unfortunately, there are 
many other factors that affect the efficiency and life of the tube: 
 

 

The silicone seal between the tube and the cap keeps moisture from infiltrating the tube. 
 

 

Excessive aluminum oxide build-up on the inner electrode can decrease the strength of the 
plasma as the oxide essentially increases the thickness of the dielectric barrier. 

 

 

The plasma discharges between the mesh and the tube slowly wears on the tube, thinning the 
dielectric barrier. Eventually, repetitive stress from the discharges can create erosion holes. 

 

 

Carbon tracking or cracks in the end cap should be gently cleaned by hand; these allow an easy 
path for current to flow and creates a short in the system. 

 

 

AtmosAir Solutions

TM

 mission is to bring and restore every indoor environment the same 

clean and pure quality air that is typically found at higher mountain elevations. 
 
AtmosAir’s unique and proven air purification process significantly reduces mold, controls 
the spread of bacteria and airborne viruses, and reduces airborne particles that evade 
normal filtration solutions.  AtmosAir equipment uses non-thermal plasma technologies to 
generate bi-polar ionization that attacks and breaks down odors and contaminants. 

 

Содержание Matterhorn Series

Страница 1: ...Installation Operations and Maintenance Guide Matterhorn Series...

Страница 2: ...negative ions into the air stream to be treated The number and size of the ionization tubes used is dependent upon the airflow size of the space and severity of the pollution and odors The AtmosAir M...

Страница 3: ...the unit s voltage rating is the same as the available voltage 220 250 VAC Install the ionization tube Gently pull the conductor strap back to allow the tube to turn freely screw the end screw of the...

Страница 4: ...d flat to duct wall to retain backer plate to secure the plate to the duct Attach the Matterhorn series system using the six 6 35mm screws The studs on the backer plate will secure the Matterhorn seri...

Страница 5: ...ctioning LED light may improperly indicate that the system is not functioning Be sure to disconnect from the mains power before performing maintenance or troubleshooting the system MaintenanceRequirem...

Страница 6: ...placed once every 24 months at a minimum as the production efficiency slowly declines over time due to the stress caused by plasma and lack of cleanliness of the electrodes Old or excessively dirty tu...

Страница 7: ...the power surge in the form of a visual or audio cue 4 It may be necessary to remove the tube s to ensure that the transformer is working properly in the absence of tubes If the fuse still blows then...

Страница 8: ...cing effectiveness or worse the seal between the dielectric material and the cap may break 6 Once the tube is secure return the conductor strap to its normal position and ensure solid contact is made...

Страница 9: ...the tube from the tube holder It is important to hold the tube only by the end cap not the core or mesh when first loosening the tube 6 Carefully remove the tube from the unit and release the conduct...

Страница 10: ...essor It may be useful to remove the tubes for improved cleaning Cleaning the general area around the tubes to remove dust dirt and debris will keep the tubes clean longer CAUTION Do not immerse the t...

Страница 11: ...ency and life of the tube The silicone seal between the tube and the cap keeps moisture from infiltrating the tube Excessive aluminum oxide build up on the inner electrode can decrease the strength of...