Thorough Clean, continued 

 
4. Clean the tube with a mild soap solution, and a soft cloth or sponge. A non-scratch scrub sponge may 
help remove sticky material. Clean any carbon tracking residue off of the end cap. Rinse or wipe the 
tube and dry thoroughly. Be sure to avoid the seal between the cap and tube and between the cap and 
the end screw when rinsing. 
 
5. Once the mesh and tube are completely dry, replace the mesh on the tube by sliding it gently over the 
tube. Be sure that the outer mesh is at least 1.25 cm from the end cap, and that both vertical seams on 
the inner and outer electrodes line up. 
 
Once the tubes are clean and completely dry, reinstall the tubes in the system.   
 

Tips on Tube Life 

 
Cleaning the tube is beneficial because it reduces stress on the transformer and also removes any dirt 
or oil that can inhibit the plasma from forming on the outside of the tube. Unfortunately, there are many 
other factors that affect the efficiency and life of the tube: 
 

 

  The silicone seal between the tube and the cap keeps moisture from infiltrating the tube. 

 

 

  Excessive aluminum oxide build-up on the inner electrode can decrease the strength of the 

plasma as the oxide essentially increases the thickness of the dielectric barrier. 

 

 

  The plasma discharges between the mesh and the tube slowly wears on the tube, thinning the 

dielectric barrier. Eventually, repetitive stress from the discharges can create erosion holes. 

 

 

  Carbon tracking or cracks in the end cap should be gently cleaned by hand; these allow an 

easy path for current to flow and creates a short in the system. 

 
 

AtmosAir Solutions

TM

 mission is to bring and restore every indoor environment the same clean 

and pure quality air that is typically found at higher mountain elevations. 
 
AtmosAir’s unique and proven air purification process significantly reduces mold, controls the 
spread  of  bacteria  and  airborne  viruses,  and  reduces  airborne  particles  that  evade  normal 
filtration solutions.    AtmosAir equipment uses non-thermal plasma technologies to generate bi-
polar ionization that attacks and breaks down odors and contaminants. 

 

Содержание FC-400 Series

Страница 1: ...Installation Operations and Maintenance Guide AtmosAir FC 400 FC 400 FM...

Страница 2: ...ated The number and size of the ionization units used is dependent upon the airflow size of the space and severity of the pollution and odors The AtmosAir FC 400 series equipment is designed for minim...

Страница 3: ...AC 50 60Hz Install the ionization tube Gently pull the conductor strap back to allow the tube to turn freely screw the end screw of the tube into the tube holder hand tight Ensure that the tube is ful...

Страница 4: ...nstallation AtmosAir FC400 series systems require approximately 7 68 watts The FC 400 series can be wired directly to blower circuits Follow proper electrical procedures guidelines and codes for provi...

Страница 5: ...he desired ion increase and appropriate system layout CAUTION A non functioning LED light may improperly indicate that the system is not functioning Be sure to disconnect quick disconnect power before...

Страница 6: ...ing 2 Year Tube Replacements The ionization tubes should be replaced once every 24 months at a minimum as the production efficiency slowly declines over time due to the stress caused by plasma and lac...

Страница 7: ...h tube for cracks pitting or other degeneration of the dielectric material that causes the dielectric to fail and arcing to occur 5 If physical inspection has not revealed the cause of failure one may...

Страница 8: ...essor It may be useful to remove the tubes for improved cleaning Cleaning the general area around the tubes to remove dust dirt and debris will keep the tubes clean longer CAUTION Do not immerse the t...

Страница 9: ...ency and life of the tube The silicone seal between the tube and the cap keeps moisture from infiltrating the tube Excessive aluminum oxide build up on the inner electrode can decrease the strength of...

Отзывы: