background image

 

 

Visibly Cleaner Air

 

AtmosAir eliminates pollutants and restores air quality in commercial, industrial and residential buildings. 
When you choose AtmosAir, you’ll refresh your indoor environment with the same clean, pure air found 
only at the highest mountain elevations. 
 

Product Overview

 

The AtmosAir FC-400 series, models FC-400 and FC-400 FM (Flush - Mount) ionization 
generators are small residential-sized units intended for installation in air conditioning systems or 
in custom-designed air distribution systems in small commercial spaces and typical residential 
houses. AtmosAir equipment is effective in reducing odors and harmful pollutants through the 
introduction of positive and negative ions into the air-stream to be treated. The number and size of 
the ionization units used is dependent upon the airflow, size of the space, and severity of the 
pollution and odors. The AtmosAir FC-400 series equipment is designed for minimal maintenance. 
The FC- 400 series has two components that require inspection and maintenance: 

1.

 

AtmosAir FC-400 series base unit comp Fuse 

2.

 

Ionization tube 

Because there are no moving parts, little maintenance is required and the systems have very low 
failure rates and minimal maintenance requirements. For more information, read the AtmosAir FC-400 
series submittal documents. 

Product Diagram

              AtmosAir FC400 equipment, labeled

 

AtmosAir FC400 System

:

 

a.

 

Female power plug receptacle 
(Quick Disconnect) 

b.

 

Ionization tube 

c.

 

System power light 

d.

 

Mounting Holes 

e.

 

Fuse Holder 

 

Overall Mounting Plate Dimensions:

 

FC-400/FC-400FM: 
152.5mmL x 89mmW x 40.6mmH 

 

FC400FM has a .200 silicone Foam 
Gasket, for sealing. 

 

76mm 

152.5mm 

Содержание FC-400 Series

Страница 1: ...Installation Operations and Maintenance Guide AtmosAir FC 400 FC 400 FM...

Страница 2: ...ated The number and size of the ionization units used is dependent upon the airflow size of the space and severity of the pollution and odors The AtmosAir FC 400 series equipment is designed for minim...

Страница 3: ...AC 50 60Hz Install the ionization tube Gently pull the conductor strap back to allow the tube to turn freely screw the end screw of the tube into the tube holder hand tight Ensure that the tube is ful...

Страница 4: ...nstallation AtmosAir FC400 series systems require approximately 7 68 watts The FC 400 series can be wired directly to blower circuits Follow proper electrical procedures guidelines and codes for provi...

Страница 5: ...he desired ion increase and appropriate system layout CAUTION A non functioning LED light may improperly indicate that the system is not functioning Be sure to disconnect quick disconnect power before...

Страница 6: ...ing 2 Year Tube Replacements The ionization tubes should be replaced once every 24 months at a minimum as the production efficiency slowly declines over time due to the stress caused by plasma and lac...

Страница 7: ...h tube for cracks pitting or other degeneration of the dielectric material that causes the dielectric to fail and arcing to occur 5 If physical inspection has not revealed the cause of failure one may...

Страница 8: ...essor It may be useful to remove the tubes for improved cleaning Cleaning the general area around the tubes to remove dust dirt and debris will keep the tubes clean longer CAUTION Do not immerse the t...

Страница 9: ...ency and life of the tube The silicone seal between the tube and the cap keeps moisture from infiltrating the tube Excessive aluminum oxide build up on the inner electrode can decrease the strength of...