Operation and Maintenance Manual - EN
EN
www.atmos.cz
EN-43
• Parameter S66
- characterizes run-out time of the burner in OPERATION mode during which the
burner stays in operation when waste gas temperature in the heat exchanger of the boiler descend
under the temperature characterized by the parameter S64.
After the time characterized by the paramater S66 is display
ALARM PELLETS – REFILL
PELLETS.
In this case check the pellet tank and fill up the fuel.
DxxPX (PXxx) boilers are designed that after fuel refill is neccesary only to turn off and on the
main swich on the boiler. So it is not neccesary fill up the pellets into the conveyor after showen
ALARM PELLETS – REFILL PELLETS
.
Function is only for DxxPX (PXxx) boilers, burner profile A25PX.
Do not change… (30 min)
• Parameter S67
- characterizes function of
R5 reserve
output similar with S6 and S14 parameters
with instaled AC07X-C additional module. Primary is this reserve used to control air pump for
pellet burner pneumatic ash cleaning system....
(15)
.
Function is also for DxxPX (PXxx) boilers, burner profile A25PX (A25PX pneu)
if:
a) S67 = 1
…. If any fault occurs in the burner and the burner is shut down,
the reserve relay will
be closed and the reserve output will be energized.
Thanks to this you can start a spare source
of energy for heating of the building as e.g. a gas, electric or oil boiler.
b) S67 = 2
….. If any fault occurs in the burner and the burner is shut down
, the reserve relay will
be opened and the reserve output will not be energized.
Thanks to this a signal can be sent to
an electrically backed up AB01 ATMOS GSM module controller that will send information that
there is a system fault or the system is not energized.
This is the opposite logic (to S6 = 1), which
means that during normal operation the reserve is energized.
c) S67 = 4
…… The reserve function as
the
reversed function of the output for the burner fan,
when the reserve
output is off, is not energized always when the burner fan is running.
This
function is always activated if
you connect the A25 burner with the AS25 set containing the
AD02 or AD03 module, which in this case controls the extraction fan of the boiler. Install the
AD02 or AD03 module under the instrument hood of the boiler and connect it electrically
between the boiler terminal board and the extraction fan, see the wiring diagram.
This setting and connection with AD02 or AD03 module and special connector (jumper to main
switch)
is standardly used for DCxxSP boilers with the function for automatic start after
wood is burnt out activated (AUTOSTART – S34 = 1 or S34 = 2). Boiler exhaust fan is run-
ning simultaneously with the pellet burner during the AUTOSTART function.
d S67 = 7
….. Reserve function as
the output function for the external worm conveyor,
when
the reserve copies the run of the external worm conveyor (cycles between time T4 and T6).
The
reserve output work independently
of the condition of the actual output for the external worm
conveyor. This means that if the standard output for the external conveyor gets damaged, the re-
serve will work independently in accordance with the same program, and therefore it can be used
as a replacement for the damaged output.
e) S67 = 8
….. Reserve function as
the output function for the external worm conveyor,
when
the reserve copies the run of the external worm conveyor (cycles between time T4 and T6).
The
reserve works in dependence on
the status of the actual output for the external worm conveyor.
Содержание A85
Страница 1: ...Operation and Maintenance Manual EN www atmos cz Operation and Maintenance Manual ...
Страница 2: ...www atmos cz Operation and Maintenance Manual EN ...
Страница 61: ...Operation and Maintenance Manual EN EN www atmos cz EN 61 20 Expanded view of the burner ...
Страница 66: ...EN www atmos cz 66 EN Operation and Maintenance Manual EN Notes ...