3. Resume oil change as described in section Oil and Filter Change in this book.
Thermostatic bypass valves
Change the thermostat of the ER system at the same interval as the thermostat of the unit.
Heat exchanger (HE)
If the temperature rise over the energy recovery system declines over a period of time with the same basic
working conditions, the heat exchanger should be inspected. To clean the oil side, soak the heat exchanger
in a degreasing solution. To remove scale formation in the water compartment, a proper descaling process
should be applied. Consult Atlas Copco.
5.1.5
Cooling water requirements
General
Cooling water needs to fulfill certain requirements in order to avoid problems of scaling,
fouling, corrosion or bacterial growth.
In open circuit cooling towers, protective measures must be taken to avoid the growth of
harmful bacteria such as legionella pneumophila when there is a risk of inhalation of the
water droplets.
No general recommendation can encompass the effects of all combinations of the various compounds,
solids and gases typically found in cooling water in interaction with different materials. Therefore the
recommendations formulated in our Cooling Water Specifications are a general guide line for acceptable
coolant quality. However, where strict limits apply, a statement is made in the specification.
The water requirements refer to untreated water. When water is treated, some parameters will change.
Water treatments should be carried out by a specialized water treatment company, taking the responsibility
for the performance of the treated cooling water and the compatibility with the materials in the cooling
circuit. This includes not only the selection of the appropriate additives, but also the correct application,
monitoring of concentrations and properties, prevention of sludge formation and maintenance of the
system. This applies also to treatment with antifreeze products. They must be provided with suitable
stabilizers and inhibitors. Specifications are also depending on the type of cooling circuit (open, once
through / recirculating with tower / closed) and on the application (Standard – max 65 °C cooling water
temperature at the outlet) or Energy Recovery (water temperature up to 95 °C).
In case water is not in line with recommended values or if any doubt, consult the manufacturer.
Cooling water parameters
1.
pH
The effect of pH is already included in the Ryznar Stability Index (RSI - see item 4 below), but also
the pH itself is subject to limitations:
pH
Type of cooling system
Materials
Standard
Energy recovery
Single pass
Containing copper
6.8
-
9.3
6.8
-
9.3
Stainless steel with carbon
steel and / or cast iron
6.8
- 9.3
6.8
- 9.3
Stainless steel only
6
- 9.3
6
- 9.3
Instruction book
90
2920 7109 23
Содержание GA 11 VSD+
Страница 1: ...Atlas Copco Oil injected rotary screw compressors GA 7 VSD GA 11 VSD GA 15 VSD Instruction book ...
Страница 2: ......
Страница 16: ...2 2 Flow diagram GA 7 VSD up to GA 15 VSD Workplace Instruction book 14 2920 7109 23 ...
Страница 88: ...Flow diagram of compressor with energy recovery system Instruction book 86 2920 7109 23 ...
Страница 136: ......
Страница 137: ......