9
Technical data
9.1
Electric cable size
Attention
Local regulations remain applicable if they are stricter than the values proposed below.
The voltage drop must not exceed 5 % of the nominal voltage. It may be necessary to
use cables of a larger size than those stated to comply with this requirement.
Recommended cable size
Cable size, IEC
Voltage
(V)
Frequency
(Hz)
Cable size
IEC
G 2
G 3
G 4
G 5
G 7
230/1
50
4 mm
2
-
-
-
-
230/3
50
1.5 mm
2
2.5 mm
2
4 mm
2
4 mm
2
6 mm
2
380/3
60
0.75 mm
2
-
1.5 mm
2
2.5 mm
2
4 mm
2
400/3
50
0.75 mm
2
1 mm
2
1.5 mm
2
2.5 mm
2
4 mm
2
Cable size, UL/CSA
Voltage
(V)
Frequency
(Hz)
Cable size
UL/CSA
G 2
G 4
G 5
G 7
230/1
60
AWG10
AWG8
AWG8
-
208/3
60
AWG12
AWG10
AWG8
AWG8
230/3
60
AWG14
AWG10
AWG10
AWG8
460/3
60
AWG14
AWG14
AWG14
AWG12
575/3
60
AWG14
AWG14
AWG14
AWG14
Instruction book
80
2920 7199 10
Содержание G 2
Страница 1: ...INSTRUCTION BOOK OIL INJECTED ROTARY SCREW COMPRESSORS G 2 G 3 G 4 G 5 G 7 ...
Страница 2: ......
Страница 15: ...2 2 Air flow Pack Air flow floor mounted Pack units Instruction book 2920 7199 10 13 ...
Страница 18: ...2 3 Oil system Oil system Pack Instruction book 16 2920 7199 10 ...
Страница 20: ...2 4 Cooling system Pack units Instruction book 18 2920 7199 10 ...
Страница 60: ...Start up Start up sheet Label on the top Instruction book 58 2920 7199 10 ...
Страница 92: ......
Страница 93: ......