51
Technical Features
Model
A03-OP1001(V1.2)
A03-
OP2301(V1.2)
A03-OP3451(V1.2)
Power Rating(VA)
1000
2300
3450
Power Rating(W)
800
1600
2400
INPUT Voltage:
160-280V (±5%)
Frequency:
50Hz±5%
OUTPU
T
Voltage:
200V/208V/220V/230V/240V
AC Voltage
Regulation
±1%
Frequency:
50Hz (±1%)
Waveform
Pure SineWave
Crest Ratio I
3:1
Harmonic
Distortion
<3% THD (liner Load)
<6% THD (Non liner Load)
TRANS
FER
AC->Battery
Zero
INV-
>ByPass
Less than 4ms (typical), max 6ms
EFFICIENCY
AC Mode=88%
Battery=83%
AC Mode=88%
Battery=85%
AC Mode=90%
Battery=88%
BATTER
Y
Voltage
24VDC
48VDC
72VDC
Capacity
12V/9.0Ah
Quantity
2
4
6
Recharge
Time
4 hours to (90%)
Type
Sealed Maintenance Free Lead Acid VRLA Type
Design
easy-swappable battery design
Charging V
27,4VDC ±1%
54,7VDC ±1%
82,1VDC ±1%
Charging I
1.0A Max
INDICATORS(Display
LCD)
Utility Normal, Backup, Battery Low and Battery Fault conditions
PROTECTION
105%<Overload AC <110%
UPS shuts down after 10 minutesat battery mode or transfer to bypass
when the utility is normal
110%<Overload AC <130%
UPS shuts down after 1 minute at battery mode or transfer to bypass