ENG
37
3
USB communication port.
4
RS232 communication port.
7
Output receptacles: connect to mission-critical loads
9
Output Terminal Block (only on A03-3451).
For socket-type outputs, simply connect devices to the outlets.
For terminal-type input or outputs, please follow below steps
for the wiring configuration:
1.
Remove the small cover of the terminal block
2.
Suggest using AWG14 or 2.1mm2 power cords for 3KVA.
Please also install a circuit breaker (20A) between the
mains and AC input of UPS in 3KVA for safety operation.
3.
Upon completion of the wiring configuration, please check
whether the wires are securely affixed.
4. Put the small cover back to the rear panel.
2.3 Setup The UPS
Step 1: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using
extension cords.
Step 2: UPS output connection
Simply plug devices to output sockets. During power failure, UPS will provide power
to connected devices.
Step 3: Communication connection
Communication port:
USB Port
RS232 Port