01.02.2017
25 / 36
KIT VARFREE -
Installation, Instalación, Installatie
EN
Electrical connections and confi gurations:
!
CAUTION:
The power must be switched off when each accessory
is connected.
Close the panel's protective cover before powering
up for confi guration.
If the boiler replaced has an OCI 420:
Put the OCI 345 in place (refer to the manual supplied with the module).
Set parameters 6600, 6601, 6640 et 6604 (
LPB network
menu on the NAVISTEM
B3000) as follows:
Set parameter 6600 with the value of parameter H605 (read on the boiler replaced).
Set parameter 6601 with the value of parameter H606 (read on the boiler replaced).
Set parameter 6640 according to the values of parameters H604.b0 and H604.b1
(read on the boiler replaced):
Old boiler
New boiler
H604.b0
H604.b1
6640
0
0
Independent
1
0
Slave without adjustment
0
1
Master
Set parameter 6604 according to the value of parameter H604.b2 (read on the boiler
replaced):
Old boiler
New boiler
H604.b2
6640
0
Stop
1
Automatic
If the boiler replaced had an AGU 2.511:
Connect the 0-10V control cable to H1-GND on the NAVISTEM B3000.
Confi gure the H1 input on the NAVISTEM B3000:
Parameter
No.
Title
Value to be programmed
5950
H1 input function
10C consum1 circ. request
5953
H1 voltage 1 value
0.0
5954
H1 function value
0
5955
H1 voltage 2 value
10.0
5956
H1 voltage 2 value
1000
(for an equivalence 10 V = 100 °C)
Содержание VARFREE
Страница 2: ......
Страница 4: ...4 36 KIT VARFREE Installation Instalación Installatie 00RNO0315 40 60 kW 80 100 kW ...
Страница 12: ...12 36 KIT VARFREE Installation Instalación Installatie 00RNO0315 3 Remontage Reassembly Montaje Hermontage ...
Страница 15: ...01 02 2017 15 36 KIT VARFREE Installation Instalación Installatie U0583823 Graisse Grease 1 2 26 57x 3 53 ...
Страница 17: ...01 02 2017 17 36 KIT VARFREE Installation Instalación Installatie U0583867 4 8 5 28 à 30 Clip 28 Etanchéité ...
Страница 18: ...18 36 KIT VARFREE Installation Instalación Installatie 00RNO0315 U0583889 ...
Страница 19: ...01 02 2017 19 36 KIT VARFREE Installation Instalación Installatie U0583890 ...
Страница 20: ...20 36 KIT VARFREE Installation Instalación Installatie 00RNO0315 U0583917 ...
Страница 21: ...01 02 2017 21 36 KIT VARFREE Installation Instalación Installatie U0584035 ...
Страница 33: ... ...
Страница 34: ... ...
Страница 35: ... ...