CONDENSINOX -
Installation, Use and Maintenance
Diagram: CX14.1
page 4 / 7
Line No.
Value
• Menu
Configuration
Start heating circuit 1
Heating circuit 1 (5710)
On
For heating circuit 1 to be effective, an actuator must be de
fi
ned even if it is
not connected:
Con
fi
gure pump Q2
Relay QX2 output (5891)
Pump HC1 Q2
Con
fi
gure the isolation valve Q1.1
Relay QX3 output (5892)
Boiler pump Q1
Con
fi
gure the cascade
fl
ow sensor B10:
Sensor input BX2 (5931)
Common
fl
ow sensor
B10
Con
fi
gure input H1
H1 input function (5950)
Request consum
circuit 1
• Con
fi
gure as master of the cascade: Menu
LPB network
Device number
Appliance address (6600)
1
Segment number
Segment address (6601)
0
Con
fi
gure the bus supply
Bus supply function (6604)
Automatic
Set the clock program
Clock operation (6640)
Master
• Menu
Heating circuit 1
Adjust the comfort setpoint
Comfort temperature setpoint (710) - - -
Set the curve slope
Heating curve slope (720) - - - (same as that
of the secondary
controller)
• Menu
Consumer circuit 1
Set the initial setpoint to use in the
event of a HC request
Cons. request initial setpoint (1859) 60°C (depends on
the Rubis setting)
• Set the heating program to permanent comfort