6 Maintenance
To ensure that your device works properly for many years, the following maintenance operations should be performed
at the start of each heating season Generally, these are performed as part of a service contract
5 3 Outdoor unit errors
In the event of an outdoor unit error:
- The user interface displays the error code "Er 66"
- View the information menu
,
- Information "
No. 18" specifies the error code for the outdoor unit "
xx" (list provided below)
Outdoor
unit error
code
Interface board
Outdoor unit
board
Error contents
LED
2
(green)
LED 1 (red)
LED
0
1 Flash
1 Flash
Off
Communication error between the interface board and the
outdoor unit: transfer error (Serial reverse)
1
1 Flash
Communication error between the interface board and the
outdoor unit: transfer error (Serial forward)
2
4 Flashes
2 Flashes
22 Flashes
Hydraulic unit exchanger temperature sensor error
3
6 Flashes
3 Flashes
18 Flashes
Inverter error
4
6 Flashes
4 Flashes
19 Flashes
Active filter error / PFC error
5
7 Flashes
1 Flash
2 Flashes
Discharge temperature sensor error
6
7 Flashes
2 Flashes
8 Flashes
Compressor temperature sensor error
7
7 Flashes
3 Flashes
5 Flashes
Exchanger temperature sensor (centre) error
8
4 Flashes
Exchanger temperature sensor (output) error
9
7 Flashes
4 Flashes
7 Flashes
Outdoor temperature sensor error
10
7 Flashes
7 Flashes
9 Flashes
Radiator temperature sensor (inverter) error
11
10 Flashes
Radiator temperature sensor (P F C ) error
12
7 Flashes
8 Flashes
6 Flashes
Pressure regulator temperature sensor error
13
8 Flashes
4 Flashes
-
Current current error
14
8 Flashes
6 Flashes
3 Flashes
Pressure sensor error / pressure switch error
15
9 Flashes
4 Flashes
13 Flashes
Current sensor error (permanent shutdown)
16
9 Flashes
5 Flashes
14 Flashes
Detection error for the position of the compressor rotor
(permanent shutdown)
15 Flashes
Compressor start-up error (permanent shutdown)
17
9 Flashes
7 Flashes
16 Flashes
Outdoor unit fan motor 1 error
17 Flashes
Outdoor unit fan motor 2 error
18
10 Flashes
1 Flash
11 Flashes
Discharge temperature protection (permanent shutdown)
19
10 Flashes
3 Flashes
12 Flashes
Compressor temperature protection (permanent shutdown)
20
10 Flashes
5 Flashes
20 Flashes
Abnormal low pressure
21
Depending on the outdoor unit error
Error originating from the outdoor unit
22
3 Flashes
2 Flashes
-
Communication error between the interface board and the HP
regulator board
6 1 Regular checks
-Periodically check the water pressure in the heating
circuit (refer to the pressure level recommended by the
installer - between 1 and 2 bar)
-
If you need to fill up and reset the pressure, check the
type of fluid originally used (if in doubt, contact your
installer)
"
If frequent refills are required it is essential that
you look for any leaks
"
The frequent supply of water risks causing
scale to build up within the heat exchanger and
degrade its performance and life
-If error
Er 76
is displayed: Call your installer
6 2 Outdoor unit check
Remove any dust from the exchanger making sure you
do not damage the blades
Check that there is nothing hindering the air flow.
"
Always check that the electric power supply is switched off before maintaining the boiler
User manual 1634 - EN
Loria 6000 heat pump