- 46 -
Trouble Type
This menu lets you turn off the Trouble Alarm, or set it to the Alarm Function.
Selectable Values: Off, Latched, Unlatched
Trouble Output Number
This menu lets you assign the digital output that activates when the channel is in
Trouble.
Selectable Values: None, 1 to 34
Alarm Deadband
This menu lets you set an alarm deadband. This deadband value applies to the
high process, low process, high deviation, and low deviation alarms for the
channel you are editing.
The alarm deadband sets the hysteresis of the alarm action which is used to
avoid intermittent alarms as the PV returns to a normal state.
Selectable Values: 0 to 255, 25.5, 2.55, .255, or .0255 depending on your input
menu setup.
NOTE
All digital outputs are combined. Therefore you can assign more than one
alarm to the same output number, and that output will be On if any of those
alarms is On.
Содержание Scan Alarm C14
Страница 10: ...10 Mechanical Installation Figure 1 Wall Mount Enclosure Dimensions ATI 0247...
Страница 11: ...11 Figure 2 Panel Mount Mounting Dimensions ATI 0257...
Страница 13: ...13 Figure 5 2 Relay Module Enclosure Dimensions 80 0040...
Страница 14: ...14 Figure 6 4 Relay Module Enclosure Dimensions 80 0036...
Страница 15: ...15 Electrical Connections SEE APPENDIX 1 IN THE BACK OF THE MANUAL FOR THE GENERAL CONNECTION DIAGRAM...
Страница 16: ...16 Figure 7 A12 UniSens Connection ATI 0256 CHANNEL 1 SHOWN...
Страница 17: ...17 Figure 8 B12 2 Wire Connections ATI 0249...
Страница 18: ...18 Figure 9 C12 17 Combustible Transmitter Connections ATI 0251...
Страница 19: ...19 Figure 10 Powered 4 20mA Input Transmitter Connections ATI 0250...
Страница 20: ...20 See Appendix 2 in back of manual for The Relay Module Wiring Diagram...
Страница 28: ...28 See Appendix 3 in the back of the manual For the Scanner Software Flowchart Diagram...
Страница 50: ...50 APPENDIX 1 General Customer Connections Diagram ATI 0248...
Страница 51: ...51 Appendix 2 Relay module wiring diagram ATI 0271...