- 9 -
RS-485 Interface
You can communicate with up to 32 Scanners on a single common loop.
Wire equipment in a single “daisy chain” using twisted shielded pairs for the RS-
485 cables. Don’t use “octopus”, or “spurs”, or “star” patterns.
Use the internal 200 Ohm terminating resistor on the RX line of the last Scanner
in the system. (If you have only one scanner, it is the last scanner in the system).
Use jumper JU1 to select the terminating resistor; place it in B position for
termination and A position for non-termination.
Connect the shields to earth ground only at the computer or other R485 interface.
Do not connect the shield to the Scanner.
NOTE
If you connect RS-485 communications and they do not function
properly,
or
if
you
have
measurement
problems
when
communications lines are connected, request additional technical
information from our Technical Service Department.
Содержание Scan Alarm C14
Страница 10: ...10 Mechanical Installation Figure 1 Wall Mount Enclosure Dimensions ATI 0247...
Страница 11: ...11 Figure 2 Panel Mount Mounting Dimensions ATI 0257...
Страница 13: ...13 Figure 5 2 Relay Module Enclosure Dimensions 80 0040...
Страница 14: ...14 Figure 6 4 Relay Module Enclosure Dimensions 80 0036...
Страница 15: ...15 Electrical Connections SEE APPENDIX 1 IN THE BACK OF THE MANUAL FOR THE GENERAL CONNECTION DIAGRAM...
Страница 16: ...16 Figure 7 A12 UniSens Connection ATI 0256 CHANNEL 1 SHOWN...
Страница 17: ...17 Figure 8 B12 2 Wire Connections ATI 0249...
Страница 18: ...18 Figure 9 C12 17 Combustible Transmitter Connections ATI 0251...
Страница 19: ...19 Figure 10 Powered 4 20mA Input Transmitter Connections ATI 0250...
Страница 20: ...20 See Appendix 2 in back of manual for The Relay Module Wiring Diagram...
Страница 28: ...28 See Appendix 3 in the back of the manual For the Scanner Software Flowchart Diagram...
Страница 50: ...50 APPENDIX 1 General Customer Connections Diagram ATI 0248...
Страница 51: ...51 Appendix 2 Relay module wiring diagram ATI 0271...