![ATI Technologies Q45P Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/ati-technologies/q45p/q45p_o-and-m-manual_2998774027.webp)
ATI
Q45P pH System
Part 4
– Configuration
27
O&M Manual
Rev-B (7/15)
Buffer Table 3
Figure 9 - Automatic pH Buffer Tables
Out#2 Mode
This function sets analog output #2 for either temperature
(default) or pH. Press ENTER to initiate user entry mode,
and the entire value will flash. Use the UP arrow key to
modify the desired value; selections include 1-C/F for
temperature or 2-pH for pH. Press ENTER to store the new
value.
Temp Units
This function sets the display units for temperature
measurement. Press ENTER to initiate user entry mode,
and the entire value will flash. Use the UP arrow key to
modify the desired display value. The choices are °F and
°C. Press ENTER to store the new value.
4.11 Control Menu [CONTROL]
The Control Menu contains all of the output control user settings:
Set 0V #1
Set 2.5V #1
Set 0V #2
4.65 pH
6.79 pH
9.23 pH
°C
pH
°C
pH
°C
pH
0
4.67
0
6.89
0
9.48
10
4.66
10
6.84
10
9.37
20
4.65
20
6.80
20
9.27
30
4.65
30
6.78
30
9.18
40
4.66
40
6.76
40
9.09
50
4.68
50
6.76
50
9.00
60
4.70
60
6.76
60
8.92
70
4.72
70
6.76
70
8.88
80
4.75
80
6.78
80
8.85
90
4.79
90
6.80
90
8.82
95
4.79
95
6.80
95
8.82