D12
EX-IR
Gas Transmitter with IR Smart Sensor
Dec 2019 ( 85-0004 Rev A)
56
Trouble
Description
Corrective Action(s)
Auto-test Fail
With
Gen. Config Err
Auto-test is enabled (Status=READY) and a
problem has been detected with the gas
generator, or the gas generator is not
compatible with the sensor’s type or range. This
problem is reported on the display during
startup, when a sensor is installed, and when a
generator is removed or installed.
4,5, or disable Auto-test (set Status to OFF)
NVM1 User CRC
An error has been detected in the user settings
stored in the transmitter’s primary non
-volatile
memory.
2,3, otherwise, reset the user memory
defaults (see Reset Menu on page 79)
If the problem persists, replace the CPU
board.
NVM1 Fact CRC
An error has been detected in the factory
settings stored in the
transmitter’s primary non
-
volatile memory.
2,3,7
NVM2 User CRC
An error has been detected in the transmitter’s
secondary non-volatile memory.
Not applicable on this transmitter
NVM2 Fact CRC
An error has been detected in the transmitter’s
secondary non-volatile memory.
Not applicable on this transmitter
Auto-test Fail
Without
Gen. Config Err
Auto-test failed after three attempts (and the
Auto-test Trouble is set to YES).
5,4,6
3W Pwr Required
Relays or RS232/485 communication is enabled,
but transmitter does not have 3-wire power
applied.
If relays are not being used, disable them
(see Relays Menu on page 74)
Xmtr Uncal
The transmitter’s factory calibration data has
become corrupted.
2,3,7
CPU Trouble
A stack overflow or other internal error occurred
in the CPU.
2,3,7
Fault Test
Trouble alarm is being tested, not an actual fault.
Gas Sensor Uncal
The gas sensor appears to be uncalibrated, which
occurs after resetting its memory.
Zero and Span calibrate the sensor.
No User Verify
A setting was not verified at the panel (within 5
minutes).
Restart the transmitter (2) and verify all
settings.
Hardware Fault
The real-time-clock, a non-volatile memory, or
some other component has faulted or been
corrupted. The transmitter will restart upon exit
from the Trouble Status Display (page 54), or
automatically from the Main Display after 5
minutes.
1,3,7,8