DEFAULT SETTINGS & MENU ITEM DESCRIPTIONS
HeatNet Control V3 2.x
DAMPER
TYPE
LINKED/COMMON
INDEPENDENT
The LINKED/COMMON setting allows one common damper to be
used and controlled by the Master Boiler. All Member boilers must
have their damper prove inputs wired as per Figure 36, Common
system damper wiring, page 58. Also see Section:
Optional
Features: Auxiliary Function Options
INDEPENDENT: Individual
dampers are in controlled by their respective boiler.
IN USE?
YES
If set to YES, then OUTPUT RELAY K5 can be used to control a
combustion air damper. The Master can control a common system
damper or an individual damper. Members control their respective
damper independent of the Master. Relay K5 is used to enable the
combustion air damper. See Figure 36, Common system damper
wiring, page 58. Needs to Prove the damper is open.
INPUT:
J12B.7
DAMPER
The damper prove input is dedicated to connect at J12B terminals 7
and 8. If using a common damper refer to the common damper
wiring diagram.
PROOF TIME
2:00
(0
– 4min)
This is the proving time in minutes for the combustion air damper
prove switch. It is sensed at J12B Pin 7. If the damper faults, a retry
will occur every 10 minutes in attempt to open the damper.
When using J12B in a common damper configuration, wiring is done
beginning with the Master boiler. J12B Pins 7,8 are connected to the
prove switch of the combustion damper. Pin 8 is supplying 24 VAC
and pin 7 is the sense input. A second wire is connected to J12B pin
7 of the Master and the other end connected to the first member
boilers J12B pin 7. If another member boiler is present, connect
another wire to the J12B Pin 7 terminal of the first member and the
other end to the second member boiler J12B pin 7. Continue this
method for each additional boiler.
RUN IN LOCAL IF:
H-NET
COMMUNICATIONS
LOST
OFF
If this entry is set to ON and the Member boiler does not see any
communications coming from the Master boiler, this boiler will run
in LOCAL. The boiler will continue to run in LOCAL until
communications are re-established or this entry is set to OFF.
LOW TEMPERATURE
SENSOR
OFF
This entry may be set to one of the temperature sensors: SUPPLY,
HEADER, RETURN, or turned OFF (default). If this entry is set to a
sensor and the temperature falls below TEMP, the boiler will
automatically start and run the water temperature up to the LOCAL
Setpoint and then shut OFF.
TEMP < 40F
40
F
35-200
F
This is the temperature that the selected sensor must fall below for
the boiler to start.
ALARM TYPE
FAULT
FAULT/WARNING
FAULT
will stop the boiler when the Delta T has exceeded its
setting.
WARNING
will allow the boiler to continue running, but produce
the Warning message.
EXCHANGERR DELTA
T
AUTO
60
F
AUTO
1 to 120
F
Settings are AUTO if running DELTA HIGH/LOW protection.
This is the maximum differential temperature the heat exchanger can
see before the LIMIT RATE feature is activated, and a log entry is
made.
76