OPTIONAL FEATURES
HeatNet Control V3 2.x
Figure 24
Local & DHW Pump connections
Local Pump/Valve
Normally Closed &
Normally Open Contacts
DHW
Normally Closed &
Normally Open Contacts
Another feature of the PUMP/VALVE OPTION is to control
a local (primary) pump using a Variable Frequency Drive.
This feature may be required when a secondary system pump
is also variable speed. To enable this feature
SETTINGS:
LOCAL PUMP:LOCAL PUMP VFD: ON
. Setting this
Option to ON will map the control signal on J4 pins 1+ and 5-
to the modulation rate. (2) wires need to be run from J4.1+
and J4.5- to the VFD‟s input connection. Ensure that the JS1
shunt jumper on the control board is in position 0-10 or 4-
20mA as required.
Combustion Air Damper
Relay K5 and the terminal J13 DAMPER is used to control a
combustion air damper. J12B.7 & .8 are used to detect the dry
contact proof switch from the damper. A proof time of up to 4
minutes can be set before the boiler can start or an alarm
condition will occur. The Combustion Damper can be setup in
the
SETTINGS: COMBUSTION AIR DAMPER
menu.
Using the LINKED/COMMON setting, the Master boiler
controls a system damper, so in the event this damper fails to
open, the system will not start. If the Master boiler‟s system
damper fails, then no call for heat will be made to the member
boiler(s).
Using the INDEPENDENT setting, each member boiler can
control its own damper and is independent of the Master
boiler when a call for heat is made to the member. This allows
for separate dampers for each boiler. They can be wired to
J12B terminals 7 and 8.
If a common system damper is used (controlled by the Master
boiler), each individual boiler must prove that the combustion
air damper is open when it is placed in LOCAL. This may be
done using J12B terminal 7 on all boilers wired to the
damper‟s prove switch. Terminal 7 is the sense input and
terminal 8 is 24 VAC. Connecting a wire to terminal 8 is not
recommended.
See Figure 36,
Common system damper wiring
, Page 58.
A separate/independent 24 VAC source is
recommended to be used for the damper prove
switch when a common system damper is used.
If you use terminal 8 to supply power from the
Master and the Master is powered OFF, no
boiler will be allowed to fire due to the loss of
power through the prove switch. A backup
boiler will also need to have the damper relay
contacts wired in parallel with the Master for
when the Master is powered OFF.
A second wire on the Master J12B terminal 7 is then
connected. The other end of this wire is then run to the first
Member boiler J12B terminal 7. If another member boiler is
present, a second wire can be connected to the first member
boiler J12B terminal 7 and the other end connected to the
other boiler J12 terminal 7. This method can be continued if
additional boilers are present. This input must be selected in
the
SETTINGS: COMBUSTION AIR DAMPER
menu.