HeatNet Control V3 1.x
Calibration
The calibration of the KN-Series boiler
should only be performed by a
licensed technician
.
All calibration settings should be adjusted based on the
boiler‟s parameters. See the Boiler Installation, Operation,
and Maintenance manual (IOM).
To enter the calibration menus, place the S2 switch on the
main control board to the CAL position. A reloading
message will be displayed and then the calibrate screen.
Be sure to set this switch back to NORM when the
calibration is complete, otherwise no external control inputs
will work (except T1-T2), the display will always indicate
CALIBRATE and some of the runtime temperatures will
not be displayed.
The MIN VFD setting, the MAX VFD setting, and the
Ignition setting can be adjusted in the calibration displays.
The values can be changed while running
ONLY IN
MINIMUM FIRE
(any, but only one of the T inputs closed).
Prior to ignition, the values may be changed, but the blower
will not operate.
The Low Fire Hold switch is located near the
Calibration switch.
While in Standby (no call for heat on inputs), the minimum
percent may be preset. To set the minimum rate while
running, any (1), and only (1) of the (T) inputs must be
closed in order to set the boiler to MINIMUM fire.
To adjust the MIN VFD as shown in the display, press the
Adjust button under the Minimum setting. The percentage
value will turn green. Adjust the Minimum value to the
desired setting using the arrow keys. The Minimum setting
is clamped to its lowest rated setting and cannot be adjusted
below this. Once you are done with this setting, press the
„X‟ key to throw out the setting or the check key to save.
To adjust the IGNITION value as shown in the display,
press the Adjust button under the IGNITION setting. The
percentage value will turn green. The Blower speed will be
set here to provide the rate for ignition. While in Standby
(no call for heat on inputs), the Ignition percent may be
preset, before firing the boiler. To set the ignition rate while
running, any (1), and only (1) of the T inputs must be closed
Pressing the Adjust key here will cause the IGNITION
setting to turn green and the boiler will ramp to the ignition
setting. Adjust it using the arrow keys and then press the
green check key to save the value. Press the „X‟ key to
discard the setting.
The Maximum value is used to set the maximum fire rate of
the boiler. To adjust the Maximum fire rate of the boiler,
press the Adjust button under the Maximum (%) value
shown in the display. The percentage value will turn green.
Then use the arrow keys to adjust the value up or down.
Adjust it using the arrow keys and then press the green
check key to save the value. Press the „X‟ key to discard the
setting.
70