SETUP & OPERATION
HeatNet Control V3 2.x
Figure 12
Mixed Boilers: Example: Condensing/Non-Condensing
PRIORITY 2
Master
2
3
4
5
FIRING MODE (MASTER)
BOILER TYPE All Boilers in Set
BOILER TYPE
(All Boilers in Set)
Non-Condensing (Set)
PRIORITY 1
Condensing (Set)
&
Figure 13
FIII Boiler Btu Chart (MBH)
MB/MW
500
750
1000
1250
1500
1750
Max Input
500
750
1M
1.25M 1.5M 1.75M
Min Input
3:1
166
250
333
416
500
583
Mod Max
80%
400
600
800
1
1.2M
1.4M
Mod Max
70%
350
525
700
875
1.1M
1.2M
Mod Max
60%
300
450
600
750
900
1.1M
Mod Max
50%
250
375
500
625
750
875M
KN Boiler Btu Chart (MBH)
KN2
KN4
KN6
KN10 KN20
KN30
Max Input
200
400
600
1MM
2M
3M
Min Input
5:1
40
80
120
200M
400
600
Mod Max
80%
160
320
480
800M
1.6M
2.4M
Mod Max
70%
140
280
420
700M
1.4M
2.1M
Mod Max
60%
120
240
360
600M
1.2M
1.8M
Mod Max
50%
100
200
300
500
1M
1.5M
Using the boiler charts and the examples used in: Mixed
System Type 1: High System Turndown, a mixed hybrid
boiler system can be designed. The Priority 1 boilers should
be setup so as to keep the non-condensing boilers from
seeing return water temperatures of less than 140F to ensure
a long heat exchanger life.