Documento riservato. Ogni modifica deve essere sottoposta all’organismo notificato. 

Confidential document. Any change must be submitted to the notified authority. 

 

Data / Date:  

Scritto/Written by 

AF 

Verificato/Verified

 

NM 

17/01/06

 

 

Concorezzo (MI) Italia 

Istruzioni ATEX / ATEX Instructions 

 

IS-014/1 Proiettori serie RLEQ . . . 
IS-014/1 Floodlight series RLEQ . . . 

 

Approvato/Approved

 

FF 

foglio 

4

 di 

sheet 

4

 of 

6

 

 

595

530

35

255

335

Morsettiera serie S_-36/I

Cert. CESI 03 ATEX 108

I M2, EEx d I 150°C

290

 

17

643

UNI 6125

Usare cavo idoneo per una 

temperatura di 90°C

To use cable for a 

temperature of 90°C"

≥ 

 

 

Installation places 

 

The floodligths series RLEQ are to be considered 
group I of electrical construction which are  
intended to be used  on mine plants, in accordance 
to EN 60079-10 
 
Installers and users are always responsible for the 
accordance on the characteristics of the places 
where installed the equipments  and to the limits 
as above.

  

 

Luoghi d’installazione 
 

I proiettori sono da considerarsi costruzioni 
elettriche

 del gruppo I quindi destinate ad 

essere utilizzate in impianti di miniera, 

luoghi 

classificati secondo le norme EN 60079-10. 
L’installatore e l’utilizzatore sono sempre 
responsabili della rispondenza delle caratteristiche 
dei luoghi d’installazione ai limiti ed alle 
caratteristiche di cui sopra. 

Manufacturing characteristics and rules 

 

The floodlight series RLEQ _ _ _/I is realized by 
two complex, body and cover make in hot  
galvanized iron sheet, the two complexes are 
united with two hinges.   
The body contains the lamp, the diffuser and the 
electric equipments. The cover is provided of 
temperate glass, sealed with silicone for hight 
temperatures and of the steel guard.    
The explosion proof is guaranteed from the 
sealing of the glass, from the joint plain between 
body and cover that it provide the lamination of 
the flame.    
The terminal block for the electric connection is 
set in external junction box, connected to the 
floodlight with a sealed nipple, so that to reduce 
the temperature of the cable entrance.   
The enclosure respect the request of the current 
rule for the explosion-proof, the rule EN 50018, 
EN 50014.   
The more frequent structure used is the following:

 

 
 
 

Caratteristiche e disposizioni costruttive. 

 

I proiettori serie RLEQ _ _ _/I sono costituite da 
due complessi corpo e coperchio realizzati in 
lamiera di ferro saldata e zincati a caldo, i due 
complessi vengono uniti con due cerniere. 
Il corpo contiene la lampada, il diffusore e le 
apparecchiature elettriche. Il coperchio è 
provvisto di vetro piano temperato, sigillato con 
silicone per alte temperature e protetto all'esterno 
da una gabbia in acciaio.  
La tenuta all’esplosione è garantita dalla 
sigillatura del vetro, dalla giunto piano di 
accoppiamento tra corpo e coperchio che permette 
la  laminazione della fiamma.  
La morsettiera per la connessione elettrica è posta 
in una cassetta di derivazione esterna, collegata al 
proiettore con un nipplo sigillato, in modo da 
ridurre la temperatura dell'entrata cavo. 
Le armature

 

rispettano i requisiti delle norme in 

vigore per l'antideflagrante, più precisamente la 
norma CEI 31-1 EN 50018, CEI 31-8 EN 50014. 
La configurazione usata più di frequente e la 
seguente: 

 
 
 

 
 

  
 
 
 
 
 
 
 
 

 
 

 
 
 
 
 
 
 
 
 
 
 
 

Содержание RLEQ Series

Страница 1: ...ons IS 014 1 Proiettori serie RLEQ IS 014 1 Floodlight series RLEQ Approvato Approved FF foglio 1 di 6 sheet 1 of 6 A D VIGANO s r l Via T Tasso 50 20049 Concorezzo MI Tel 0039 039 61153 1 R A Fax 0039 039 6040695 E mail info ad vigano com http www ad vigano com ATEX Instructions Floodlights series RLEQ I M2 EEx d I 163 C 191 C Test Certificate INERIS 06 ATEX 0001 Istruzioni ATEX Proiettori serie ...

Страница 2: ... correct installation and connection Refer to the same for detailed instructions Usage Limitation The floodlight are manufactured in accordance to EEx d I 163 C 191 C protection The protection level covering every single box is indicated on the certification and rating Istruzioni per l uso ATEX Generalità Le misure di sicurezza e le apparecchiature utilizzate sul posto d installazione esercizio e ...

Страница 3: ...nsability that the containers are manufactured at a state of art for what concerns safety and are in accordance to applicable CE Directives and that verifications and individual tests as required and indicated on the components certificates have been carried out with positive result Targa dati e marcatura ATEX Tutti i proiettori sono dotati di targhe indelebili e durevoli sono fissate lateralmente...

Страница 4: ...h two hinges The body contains the lamp the diffuser and the electric equipments The cover is provided of temperate glass sealed with silicone for hight temperatures and of the steel guard The explosion proof is guaranteed from the sealing of the glass from the joint plain between body and cover that it provide the lamination of the flame The terminal block for the electric connection is set in ex...

Страница 5: ...damenti Verifications and maintenance The verification and maintenance of the electrical equipments in places with explosion dangers must be performed following the instructions of EN 60079 17 rule Before any maintenance intervention which requires the opening of the enclosure to access the internal equipments power must be switched off for this the user will have to foresee inside a custody with ...

Страница 6: ...le entries must be made using cable glands EEx d certified in accordance to the EN 50014 and EN 50018 rules The used cable has to have a use temperature greater or equal to 90 C The cable glands must be correctly choosen depending on the type of equipment and the cable type The cable glands must be duly tightened so that the sealing rings reach the necessary pressure a To avoid the transmission of...

Страница 7: ...18 2000 A1 Standards nazionali o documenti normativi applicati applied national standards or normative documents EN 60598 2 5 1998 EN 60529 1997 A1 Ente notificato Notified Body CESI 0722 Notifica della produzione EC Type Examination CESI 03 ATEX 019 Q _____________________________________________________________ Technical File no INERIS 06 ATEX 0001 _______________________________________________...

Отзывы: