System architectures
6.1
Data bus architecture
In this system gas detectors are connected to the bus via T-connectors S2.
Figure 2: Arrangement of gas detectors according to the data bus architecture
Detailed schematic diagrams in an editable format can be found on our
website.
7
Life cycle
7.1
Transportation
The device can be shipped in the same way as new equipment of that type. If the original package or
another protecting means (e.g. corks) is unavailable the conveyed equipment must be secured against
shocks, vibrations or moisture by means of adequate methods and material at the own responsibility of the
sender.
The device can be conveyed under environmental conditions as described in Table 5.
7.2
Installation
7.2.1
Deployment of gas detectors
Deployment of gas detectors must be determined by the system designed with consideration to the
following rules:
installation of detectors is recommended somewhere 30 cm below the topmost point of the
ceiling – methane is lighter than air and tends to migrate upwards,
detectors should me mounted at locations where gathering (accumulation) of gas is expected due
to architectural properties of the facility (e.g. in the facility part that is separated from the entire
space by means of walls or other structural components),