DIS. 0534026   COD. 27102280 

Istruzione / User’s Manual / Manuel d’utilisation

 

Pag.1/8

 

 

Centralina gas per centrali termiche 
Gas detector for heating plants 
Centrale détection de gaz pour chaufferies  

 

 

 

GECA Srl Via E. Fermi 98, 25064 Gussago (Brescia) Italy http://www.gecasrl.it Tel:+39 030/3730218  Fax: +39 030/3730228

 

 

 

 

CTR137

 

 

 

 
 
 

 

Caratteristiche tecniche / 

Technical specifications

 / 

Caractéristiques techniques

 

Alimentazione / 

Power supply / Alimentation

 

230Vac (-15/+10%) 50Hz / 3VA 

12÷24Vac (-15/+10%) 50Hz / 3 VA 

12÷24Vcc (-10/+15%) / 1,5 W 

Sensore / 

Sensor Type / Capteur

 

Catalitico / 

Catalityc / Catalytiques

 

Campo di misura / 

Standard Range / Champ de mesure

 

0 ÷ 20% LIE / LEL 

Vita media in aria pulita / 

Average Life in fresh air / Vie moyenne en air pur

 

5 anni

 / years / ans

 

Intervento allarme 
1st 

Alarm intervention / Seuil d'intervention de alarme

 

10% LIE / LEL 

Intervento blocco 
2nd 

Alarm intervention / Seuil d'intervention de blocage

 

20% LIE / LEL 

Contatti relè /

 Contacts rating / Contact relais

 

230Vac 3A SPDT 

Tempo di risposta T

90

 / 

Response Time 

T

90

 /

  

Temps de réponse T

90

 

< 30 secondi / 

seconds / secondes 

Temperatura-Umidità di funzionamento  
O

peration Temp-Humidity / Temp. et humidité de fonctionnement

 

-10 ÷ +50 °C / 5 ÷ 90 % RH 

non condensata / 

non condensed / non condensée

 

Temperatura-Umidità di immagazzinamento  

Storage Temp-Humidity / Temp. et humidité de stockage

 

-25 ÷ +55°C / 5 ÷ 95 % RH 

non condensata / 

non condensed / non condensée

 

Dimensioni / 

Size / Dimensions

 

160 x 125 x 80 mm / IP65 

 

 
 

 

 DESCRIZIONE ............................................................................................................................ 2

 

FUNZIONAMENTO ................................................................................................................................. 2

 

INSTALLAZIONE.................................................................................................................................... 2

 

AVVERTENZE ........................................................................................................................................ 3

 

VERIFICA FUNZIONAMENTO ............................................................................................................... 3

 

GB 

 DESCRIPTION............................................................................................................................. 4

 

OPERATIONAL DESCRIPTION ............................................................................................................. 4

 

INSTALLATION ...................................................................................................................................... 4

 

WARNING............................................................................................................................................... 5

 

FUNTIONAL TESTING ........................................................................................................................... 5

 

 DESCRIPTION............................................................................................................................. 5

 

FONCTIONNEMENT............................................................................................................................... 6

 

INSTALLATION ...................................................................................................................................... 6

 

AVVERTISSEMENT................................................................................................................................ 7

 

Modello 

Model 

Modele

 

Tarato per 

Calibrated for

 / 

Tarée pour

 

CTR137M 

Metano / 

Methane

 / 

Méthane

 

CTR137G 

GPL / LPG 

 

Summary of Contents for CTR137M

Page 1: ...ntervention de alarme 10 LIE LEL Intervento blocco 2nd Alarm intervention Seuil d intervention de blocage 20 LIE LEL Contatti rel Contacts rating Contact relais 230Vac 3A SPDT Tempo di risposta T90 Re...

Page 2: ...one e nel caso in cui essa sia scattata si spegner il Led giallo e si disattiver il rel FAULT vedi sezione Guasti pi avanti Ripristino dopo un Allarme la centralina torner al funzionamento normale sol...

Page 3: ...e causano una temporanea perdita di sensibilit Questi inibitori sono gli Alogeni l Idrogeno solforato il Cloro gli Idrocarburi clorurati Trielina o Tetracloruro di carbonio Dopo un breve tempo in aria...

Page 4: ...nditions and or switch off the siren push the RESET button Buzzer the PREAL relay will be deactivated and the Red Led flashes only if the gas concentration is higher than 10 of LIE After 20 seconds bo...

Page 5: ...vity These inhibitors include Hydrogen sulphide Chlorine Chlorinated hydrocarbons and halogenated compounds The sensitivity is recovered after a short period of running in clear air FUNTIONAL TESTING...

Page 6: ...ngement R armement apr s une d alarme La centrale revient au fonctionnement normal si la concentration de gaz est inf rieure 10 de la LIE Le relais ALARME sera d sactiv le 3 et 4 led rouge s tendent S...

Page 7: ...ique il est conseill d effectuer une v rification de fonctionnement tous les 6 12 mois ATTENTION cette proc dure doit tre ex cut e avec une extr me attention par un personnel autoris et comp tent car...

Page 8: ...norm ferm e 230Vca NC C NA NC C NA NC C NA L N SE301A PREAL ALARM Valvola NC FAULT AUX Fig 4 Collegamento con valvola a riarmo manuale Norm Aperta Wiring diagram with a normally open manual resetting...