Chapter 5. RS-232 / Telnet Commands
73
Switch Outlet Status
The Switch Outlet Status command allows you to change the power status of
an outlet on the eco PDU.
The formula for Switch Outlet Status commands is as follows:
C Control
+
[Enter]
1. For example, if you want to switch off outlet 04 immediately, type the
following:
sw o04 off imme [Enter]
2. For example, if you want to switch on outlet 12 with the time delay set for
the outlet, type the following:
sw o12 on delay [Enter]
3. For example, if you want to reboot outlet 08, type the following:
sw o08 reboot [Enter]
The following tables show the possible values for the Switch Outlet Status
commands:
Command
Description
sw
Switch outlet status command
Outlet
Description
o
Outlet command
xx
PDU outlet number
xx: Outlet on PDU
Example: o02
Control
Description
on
Switch outlet on
off
Switch outlet off
reboot
Switch outlet off and then
switch outlet on
Option
Description
imme
Switch outlet status
immediately
delay
Switch outlet status with time
delay set for the outlet
Содержание PE6208AV
Страница 1: ...PE6108AV PE6208AV PE8208AV 8 Outlets eco PDU User Manual www aten com...
Страница 20: ...PE6108AV PE6208AV PE8208AV User Manual 10 This Page Intentionally Left Blank...
Страница 76: ...PE6108AV PE6208AV PE8208AV User Manual 66 This Page Intentionally Left Blank...
Страница 91: ...Appendix 81 Do not connect the RJ 11 connector marked Sensor to a public telecommunication network...
Страница 112: ...PE6108AV PE6208AV PE8208AV User Manual 102...