Chapter 2. Hardware Setup
15
Power Cord Installation (PE6208AVX)
The PE6208AVX eco PDU provides terminal blocks that allow for custom
power cord installation. Please read the following precautions before
proceeding to the installation instructions.
Before Installation
WARNING! Unless you are a licensed electrician, DO NOT perform wiring
assembly for this product. Assembly or attempted assembly by unlicensed
electricians may result in fire, personal injury, electrical shock, and death. If
you are not a qualified electrician (having appropriate licensing and insurance)
- STOP NOW. ATEN is not responsible for any damages to equipment or loss
of data due to improper installation.
Cord Selection
The preferred cable is a flexible 3.0m long (max), 14 AWG cord, or a
1.5mm
2
, 3G flexible cord (e.g.: H05VV-F, 250V.), with a diameter of 7 -
10mm.
The rated ampacity of the power cord must be greater than or equal to the
product’s rated ampacity marked on its nameplate.
The number of wires in the power cord must match the number of
terminals (including the ground terminal).
The power cord may be permanently connected to the power supply
subject to local regulatory agency approval.
Plug Selection
If a plug is to be attached to the power cord, the plug chosen should be
250V, 16A, 3C, IEC 60320 C19.
For all other locations, subject to local regulatory agencies policies, the
plug’s rated ampacity needs to be the same as the products rated ampacity.
Содержание PE6208AV
Страница 1: ...PE6108AV PE6208AV PE8208AV 8 Outlets eco PDU User Manual www aten com...
Страница 20: ...PE6108AV PE6208AV PE8208AV User Manual 10 This Page Intentionally Left Blank...
Страница 76: ...PE6108AV PE6208AV PE8208AV User Manual 66 This Page Intentionally Left Blank...
Страница 91: ...Appendix 81 Do not connect the RJ 11 connector marked Sensor to a public telecommunication network...
Страница 112: ...PE6108AV PE6208AV PE8208AV User Manual 102...