Chapter 4. Browser Operation
41
When you have finished making your configuration settings, click
Save
.
MAC Address
In order to use either of the Safe Shutdown and Restart methods
the MAC address of the computer connected to the outlet must be
filled in here.
Auto Ping Method
Auto Ping Method
pings a device at specified intervals and if there
is no response (Request timed out) the PDU automatically powers
cycles the outlet (off and then on).
Config:
Use this drop-down menu to select the type of device you
want to ping:
Sky/SkyHD/SkyQ (DLNA)
will auto configure the
Method
and
Port
settings and they cannot be changed.
Use
Other
to ping any other network device.
Method:
Use the drop-down menu to select:
None
to disable Auto Ping Method.
Ping
to ping a specified IP address.
Telnet
to ping the port of a specified IP address.
Interval Time:
Enter the number of minutes to elapse between
each auto-ping that is sent to test the network device.
Retries:
Enter the number of power cycles to attempt if the device
cannot be pinged after the initial power cycle. If the device still
cannot be pinged after the specified number of retries, the PDU
will stop pinging the device and shut off the outlet. To restart Auto
Ping Method, you must set the Auto Ping
Method
to
None
,
reselect Ping or Telnet, and then power on the outlet.
IP Address:
Enter the IP address of the device you want to ping.
Port:
Enter the port number of the device you want Telnet to ping.
This option is available when Telnet is selected.
Holiday Mode
Use this drop-down menu to select the outlet’s Holiday Mode.
When Holiday Mode is enabled, each outlet will be set to the
selection chosen for it:
POWER OFF
or
POWER ON
.
When Holiday Mode is disabled, the outlets return to the outlet
status setting before Holiday Mode was enabled.
To enable/disable Holiday Mode, press and hold Power Control
Button (
8
) in for more than 8 seconds. This is a toggle setting.
Heading
Meaning
Содержание PE6208AV
Страница 1: ...PE6108AV PE6208AV PE8208AV 8 Outlets eco PDU User Manual www aten com...
Страница 20: ...PE6108AV PE6208AV PE8208AV User Manual 10 This Page Intentionally Left Blank...
Страница 76: ...PE6108AV PE6208AV PE8208AV User Manual 66 This Page Intentionally Left Blank...
Страница 91: ...Appendix 81 Do not connect the RJ 11 connector marked Sensor to a public telecommunication network...
Страница 112: ...PE6108AV PE6208AV PE8208AV User Manual 102...