PE6108AV / PE6208AV / PE8208AV User Manual
40
Delay Time (sec)
Power ON
Sets the amount of time the eco PDU waits after the Power Button
is clicked (see
, page 32), before it turns
on the power to the outlet. You must check the
Enable Power On
Time Schedule Setting
box for this setting to take effect.
Power On Time Schedule Settings
Note:
The default delay time is 0 seconds; the maximum is 999
seconds. When a series of outlets are scheduled to be powered
up, they turn on in sequence with a default delay of 10
milliseconds between each outlet.
Delay Time (sec)
Power OFF
Sets the amount of time the eco PDU waits after the Power Button
is clicked (see
, page 32), before it turns
off the power to the outlet.
For the
System after AC Back
option (see below), after the delay
time expires, the eco PDU waits another fifteen seconds, then
shuts the computer down.
The default delay time is 15 seconds. The maximum delay time is
999 seconds.
Remote Turn ON
Method
Use the drop-down menu to select one of the choices, below:
Wake on LAN:
This is a Safe Shutdown and Restart option. If this
is selected, when an Outlet is turned Off, the eco PDU first sends
a message to the computer telling it to prepare for a shutdown; it
then waits for the amount time set in the
Power Off Delay
field to
give the OS time to close down before the computer is powered
down to standby mode.
Likewise, when the Outlet is turned On, the eco PDU waits for
the amount time set in the
Power On Delay
field, then sends an
Ethernet message to the computer connected to the Outlet
telling the computer to turn itself On.
Note:
For Safe Shutdown and Restart, the computer must be
running Windows (98 or higher), or Linux, and the
Safe
Shutdown
program (available by download from our website),
must be installed and running on the computer.
System after AC Back:
This is a Safe Shutdown and Restart
option. If this is selected, when an Outlet is turned Off, the eco
PDU first sends a message to the computer telling it to prepare
for a shutdown; it then waits for the amount time set in the
Power
Off Delay
field to give the OS time to close down before the
computer is powered down.
When the Outlet is turned On, the eco PDU waits for the amount
time set in the
Power On Delay
field, then sends power to the
server. When the server receives the power, it turns itself on.
Note:
For Safe Shutdown and Reboot, the computer must be
running Windows (98 or higher), or Linux, and the
Safe
Shutdown
program (available by download from our website),
must be installed and running on the computer.
Kill the Power:
If this option is selected, the eco PDU waits for the
amount time set in the
Power Off Delay
field, and then turns the
Outlet's power Off. Turning the power off performs a cold (non-
safe) shutdown.
Heading
Meaning
Содержание PE6208AV
Страница 1: ...PE6108AV PE6208AV PE8208AV 8 Outlets eco PDU User Manual www aten com...
Страница 20: ...PE6108AV PE6208AV PE8208AV User Manual 10 This Page Intentionally Left Blank...
Страница 76: ...PE6108AV PE6208AV PE8208AV User Manual 66 This Page Intentionally Left Blank...
Страница 91: ...Appendix 81 Do not connect the RJ 11 connector marked Sensor to a public telecommunication network...
Страница 112: ...PE6108AV PE6208AV PE8208AV User Manual 102...