UPS User Manual
38
Acceptable Input Voltage Range
Setting
Display: 19
Display: HS
Parameter 2: Acceptable high voltage
point and acceptable low voltage point
for
input voltage range. Press the Up or Down
key to adjust the values.
HLS:
Input high voltage point
For 200/208/220/230/240 VAC models:
280/290/300:
setting the high voltage point
in parameter 2. (Default: 300Vac)
For 100/110/115/120/127 VAC models:
140/145/150:
setting the high voltage point
in parameter 2. (Default: 150Vac)
LLS:
Bypass low voltage point
For 200/208/220/230/240 VAC models:
110/120/130/140/150/160:
setting the low
voltage point in parameter 2. (Default:
110Vac)
For 100/110/115/120/127 VAC models:
55/60/65/70/75/80:
setting the low voltage
point in parameter 2. (Default: 55Vac)
Exit
Display: 00
Exit UPS Setting.
Parameter 1 & Interface Display
Parameter 2 Description