Chapter 4. Browser Operation
39
PDU Status
All eco PDU models support PDU device level monitoring. The
PDU Status
section allows you to set up a power management configuration for the PDU
device as a whole:
PDU Threshold Settings
These fields are used to set the maximum, minimum, and fluctuation
threshold settings for Aggregate Current, Voltage, Power, and Aggregate
Power Dissipation. If a range falls below the minimum setting, or exceeds
the maximum setting an alarm is triggered.
Breaker
status (ON / OFF) displays here.
Voltage Frequency
is displayed here in Hz.
On / Off / Reboot
You can manually turn the device On and Off from this page by clicking
the radio buttons. To Reboot the device, enable the Reboot checkbox and
click on Save (located at the bottom of the page).
Sensor 1 / Sensor 2
If you have sensors installed in your installation, use these fields to set the
maximum, minimum, and fluctuation threshold settings for Temperature,
Humidity, and Pressure.
Note:
Sensors are optional accessories. Check with your dealer for
information about NRGence eco Sensors software.
Содержание eco PE Series
Страница 19: ...Chapter 1 Introduction 9 Components PE5324LB PE5324LG PE5324LJ Front View 1 5 6 2 3 3 3 4 7 4 4...
Страница 21: ...Chapter 1 Introduction 11 PE5324LKJA Front View 1 4 5 6 4 4 2 3 7 3 3...
Страница 23: ...Chapter 1 Introduction 13 PE5324LJA Front View 1 4 5 2 3 6 3 3...
Страница 25: ...Chapter 1 Introduction 15 PE6324LB PE6324LG PE6324LJ Front View 1 5 8 6 8 8 7 2 3 3 3 4 4 4...
Страница 27: ...Chapter 1 Introduction 17 PE6324LJA 1 4 7 5 7 7 6 2 3 3 3...
Страница 29: ...Chapter 1 Introduction 19 PE5340SLB PE5340SLG PE5340SLJ Front View 1 4 5 6 2 3 3...
Страница 31: ...Chapter 1 Introduction 21 PE5340SLJA Front View 1 4 5 6 2 3 3...
Страница 38: ...eco PDU PE Low Profile Series User Manual 28 3 2 1 4 1...
Страница 78: ...eco PDU PE Low Profile Series User Manual 68 This Page Intentionally Left Blank...