ATC Mini Chiller - ModBUS Communication Protocol
ATC MINI Chiller Modbus Protocol v1 - 03 May 2019
7
3 Register Map
The ATC MINI Chiller slave address, register start address, write permission, baud rate, parity, duplex and
enable are set in the ModBUS Parameter submenu accessible from the MINI Chiller user interface touch screen.
REG
HEX
WRITE/READ FUNCTION
NOTE
0
00
WR/RD
Process Stop/Start
Integer
– Stop=0, Start =1, use function 6 to write, 3 to read
1
01
WR/RD
SET Temperature
Float IEEE-754, use function 16 to write, 3 to read
2
02
3
03
RD Only
OUT Temperature
OUT PT100 Sensor, Float IEEE-754, use function 3 to read
4
04
5
05
RD Only
Subcooling Temperature
Subcooling PT100 Sensor, Float IEEE-754, use function 3 to read
6
06
7
07
RD Only
Pressure Value
Pressure, Float IEEE-754, use function 16 to read
8
08
9
09
RD Only
Calibrated fan speed
Integer %, use function 3 to read
10
0A
RD Only
Calibrated compressor speed
Integer %, use function 3 to read
11
0B
RD Only
Compressor error state
Integer see Mini Chiller product spec for values
12
0C
RD Only
Upper level switch state
Reg 13 = 0
– empty, 12=0 and 13=1 – half, 12=1 and 13=1 – full
13
0D
RD Only
Lower level switch state
14
0E
RD Only
Maintenance 1 day
1-31
15
0F
RD Only
Maintenance 1 month
1-12
16
10
RD Only
Maintenance 1 year
1-65,535
17
11
RD Only
Maintenance 1 status
flag (0 (date done) / 1 (date due))
18
12
RD Only
Maintenance 2 day
1-31
19
13
RD Only
Maintenance 2 month
1-12
20
14
RD Only
Maintenance 2 year
1-65,535
21
15
RD Only
Maintenance 2 status
flag (0 (date done) / 1 (date due))
22
16
RD Only
Maintenance 3 day
1-31
23
17
RD Only
Maintenance 3 month
1-12
24
18
RD Only
Maintenance 3 year
1-65,535
25
19
RD Only
Maintenance 3 status
flag (0 (date done) / 1 (date due))
26
1A
RD Only
Maintenance 4 day
1-31
27
1B
RD Only
Maintenance 4 month
1-12
28
1C
RD Only
Maintenance 4 year
1-65,535
29
1D
RD Only
Maintenance 4 status
flag (0 (date done) / 1 (date due))
30
1E
RD Only
Maintenance 5 day
1-31
31
1F
RD Only
Maintenance 5 month
1-12
32
20
RD Only
Maintenance 5 year
1-65,535
33
21
RD Only
Maintenance 5 status
flag (0 (date done) / 1 (date due))
34
22
RD Only
Maintenance 6 day
1-31
35
23
RD Only
Maintenance 6 month
1-12
36
24
RD Only
Maintenance 6 year
1-65,535
37
25
RD Only
Maintenance 6 status
flag (0 (date done) / 1 (date due))
38
26
RD Only
Maintenance 7 day
1-31
39
27
RD Only
Maintenance 7 month
1-12
40
28
RD Only
Maintenance 7 year
1-65,535
41
29
RD Only
Maintenance 7 status
flag (0 (date done) / 1 (date due))
This Register Map is Copyright 2019 Applied Thermal Controls.
Please refer to the MINI Chiller Parameter Menu settings to establish the specific use of Maintenance 1 to 7.
Annex L-11M 190503 SA00011M RS485 ModBUS RTU for Mini