PRODUCT SPECIFICATIONS
Attribute
Unit
Value
Dimensions (W*D*H)
mm
180*435*380
inch
7.1*17.1*15
Weight
kg
20
lbs.
44.1
Heat transfer fluid
volume
mL
650
USGal
0.172
Cooling capacity
(T
ambient
+20°C / +68°F)
(T
setpoint
+20°C / +68°F)
W
500
BTU/h
1706
RT
0.142
Temp. adjustment ±°C
0.1
Settable temp. range °C
+4 to +35
Optional temp. range °C
-10 to +65
Power supply
requirement
VAC
100-240
Hz
50/60
A
1@240VAC
2@115VAC
Sound pressure level dBa
35-64
Controller screen size inch
4.3” diagonal
Auto-diagnostic
functions
PID, compressor and fan
percentage utilization.
Fridge system high pressure
value.
Compressor error states.
Export system log via USB.
Fluid fittings (standard) Pushfit 12mm
Fluid fittings (option) Valved QR
9.5mm (3/8”)
Low fluid level alarm Visual, 3 level
Controller screen
Resistive type, glove-friendly,
pen-friendly.
Tool-less access No
Overtemperature
protection
Hardware limited
Software settable
Compressor overload
protection
Via PCB function
Overcurrent protection Fused, 2* T6.3A H250V
Rated duty cycle Continuous
Compatible heat
transfer fluids
DI water, propylene glycol
mixes, Hexid A4 & A6
Opening section MPC3, 10, 18 & MPD3
3